Electrical wiring |
UniLine EC, KaControl model (*C1)
The function of the multifunctional inputs AI1, AI2 and AI3 can be
configured using parameter settings.
Function AI1 – Parameter P15
Parameter PI5 is used to set the function of the multifunctional input AI1.
10.12.5 Function of multifunctional inputs AI1, AI2 and AI3
Position
Standar
d
Min
Max
Unit
P15
function AI1
0 = not used (input disabled)
1 = NTC outside air sensor
2 = NTC cold/hot water sensor (clip-on sensor)
3 = NTC cold water sensor (clip-on sensor)
4 = NTC hot water sensor
5 = NTC external Room temperature sensor / induction sensor
6 = 0..100 K ohm fan actuation
7 = 0..100 K ohm temperature setpoint
8 = 0..100V BMS winter/summer control
9 = 0..100V BMS winter control
19 = external frost protection monitor contact closed
no frost
10 = Eco/Day mode
contact open
Day
11 = no function
contact open
no function
12 = condensation alarm
contact open
no condensation
13 = general alarm
contact open
no alarm
14 = external frost protection monitor contact open
no frost
15 = Eco/Day mode
contact open
Day
16 = no function
contact closed
no function
17 = condensation alarm
contact closed
no condensation
18 = general alarm
contact closed
no alarm
19 = external frost protection monitor contact closed
no frost
0
0
19
The multifunctional input AI1 can only be set using parameter P15 if DIP
switch no. 6 is set to ON! The setting of the DIP switches is described in
section 10.