Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains
Electrical wiring |
UniLine EC, KaControl model (*C1)
10.14 Parameter list for control PCB
Position
Standard
Min
Max
Unit
Remark
P000 Software version
-
0
255
-
-
P001 Basic setpoint for setpoint input ± 3K
22
8
32
°C
32
P002 Switching on and off hysteresis of valves
3
0
255
K/10
1
P003 Neutral zone in 4-pipe system (only in automatic mode)
3
0
255
K/10
3
P004 Cooling without fan assistance (natural convection)
0
0
255
K/10
0
P005 Heating without fan assistance (natural convection)
5
0
255
K/10
3
P006 Fan hysteresis On/Off (only in ventilation mode)
5
0
255
K/10
5
P007 P-band heating
15
0
100
K/10
17
P008 P-band cooling
20
0
100
K/10
20
P009 Offset to base setpoint for setpoint input 3K
3
0
10
K
0
P010 Clip-on sensor: limit temperature to activate fan stages 1 and 2 in heating mode 29
29
0
255
°C
29
P011 Clip-on sensor: limit temperature to activate fan stages 3 and 4 in heating mode 31
31
0
255
°C
31
P012 Clip-on sensor: limit temperature to activate fan stage 5 in heating mode
33
0
255
°C
33
P013 Clip-on sensor: hysteresis for limit temperatures P010, P011, P012, P014
10
0
255
K/10
10
P014 Clip-on sensor: limit temperature to activate fan stages in cooling mode
18
0
255
°C
18
P015 Function of input AI1
0
0
19
-
0
P016 Function of input AI2
0
0
19
-
0
P017 Function of input AI3
0
0
9
-
0
P018 Temperature increase of cooling setpoint in Eco mode
30
0
255
K/10
30
P019 Temperature drop of heating setpoint in Eco mode
30
0
255
K/10
30
P020 ADC limit coefficient
6
0
15
-
6
P021 ADC average coefficient
6
0
15
-
6
P022 Activation / deactivation of sun symbol in Comfort mode
0
0
1
-
0
P023 Difference for compensation when cooling
0
-99
127
K/10
0
P024 Coefficient for compensation when cooling
0
-20
20
1/10
0
P025 Difference for compensation when heating
0
-99
127
K/10
0
P026 Coefficient for compensation when heating
0
-20
20
1/10
0
P027 Fan setting: maximum running time of manual fan operation
0
0
255
Min
0
P028 Rinsing function: fan stage during the rinsing function
2
1
5
-
2
P029 Activation of continuous fan mode
0
0
1
-
1
P030 Temperature ventilation release
12
0
255
°C
12
P031 Ventilation interval
27
0
255
°C
27
P032 Rinsing function: maximum standstill period of fan
15
0
255
Min
15
P033 Rinse function: duration of rinsing function
240
0
255
s
240
P034 Rinse function: activation in operating modes
0
0
3
-
0
P035 Time the fan runs at stage 1 after change of operating mode
0
0
255
s
0
P036 Type of setpoint setting
0
0
1
-
1
P037 Display
1
0
7
-
0
P038 Lock/deactivate function on control unit
64
0
255
-
105
P039 Function of digital output V2 (in 2-pipe system)
0
0
3
-
1
P040 Valve actuation via pulse width modulation
0
0
1
-
0
P041 Reset time of PI controller to actuate the fan in automatic fan mode
0
0
20
Min
0
P042 Fan setting: locking and releasing fan stages
0
0
127
-
3
P043 Function of digital input DI1
1
0
14
-
1