52 II_PAXOS_V001_20161007_EN
PAXOS advance Series
Electrical Installation
Installation Instructions
INx
GND
6.8 kΩ
6.8 k
Ω
ext.
I/O-Box
INx
GND
ext.
I/O-Box
5.3.2 I/O-Box connection data
Terminal
Description
Load capacity/comments
1 (IN1) / 2 (GND) **
Input 1
Standard: Remote lock
12 ... 24 VDC (min. 5mA)
*
Connection without tamper
monitoring circuit (factory
configuration):
**
Connection with tamper
monitoring circuit (factory
configuration):
Important: the use of the tamper
monitoring circuit requires an
external voltage supply!
3 (IN2) / 4 (GND) *
Input 2
Standard: Bypass opening delay
Note: the bypass opening delay
is immediately cancelled, if the
input signal switches back into
the passive status.
5 (IN3) / 6 (GND) *
Input 3
Standard: Time lock interruption
Note: the time lock interruption
is valid for 2 minutes from turn-
on time.
16 (IN4) / 17 (GND) *
Input 4
Standard: external tamper
contact
18 (IN5) / 19 (GND) *
Input 5
Standard: not assigned
20 (IN6) / 21 (GND) *
Input 6
Standard: not assigned
31 (IN7) / 32 (GND) *
Input 7
Standard: not assigned
33 (IN8) / 34 (GND) *
Input 8
Standard: not assigned
7 (OUT1) / 8 (OUT1)
Output 1
Standard: Lock 1 open
Voltage load at the output:
max. 24 VAC
Current load at the output:
max. 0.4 A at 25°C
max. 0.3 A at 50°C
Note: the standard setting (NC:
normally closed) can be changed
via the AS384 Management-Suite
Software, if the standard (see
description in the table) does not
apply.
9 (OUT2) / 10 (OUT2)
Output 2
Standard: All locks and door bolts
open
11 (OUT3) / 12 (OUT3)
Output 3
Standard: Tamper resistance
surveillance input
22 (OUT4) / 23 (OUT4)
Output 4
Standard: Penalty lock
24 (OUT5) / 25 (OUT5)
Output 5
Standard: Duress alarm impulse
(Impuls length 2..3 seconds)
35 (OUT6) / 36 (OUT6)
Output 6
Standard: Duress alarm static
37 (OUT7) / 38 (OUT7)
Output 7
Standard: Battery compartment
open
OUTx
OUTx
ext.
I/O-Box
NC