NOTE:
The calculations in this topic represent the maximum power requirements that you need
to budget for your MX10016 router configuration. The actual power consumption of your router
can be less than the calculated results shown here and will vary based on the hardware and software
configuration of your router, the amount of traffic passing through the line cards, and environmental
variables such as room temperature.
Before you begin these calculations:
•
Ensure that you understand different router configurations. See
.
•
Ensure that you know the power requirements of different router components. See
for MX10016 Components” on page 97
.
This topic describes these tasks:
1.
How to Calculate the Power Consumption of Your MX10016 Configuration | 98
2.
How to Calculate the Number of Power Supplies Required for Your MX10016 Configuration | 100
How to Calculate the Power Consumption of Your MX10016 Configuration
Use the following procedure to determine the maximum power you need to supply to the router. To
calculate the maximum power consumption, you first determine the combined maximum internal power
requirements of all the router components and then divide this result by the output power of the power
supply.
To calculate the maximum power consumption:
1. Determine the maximum power consumption of the base chassis components (that is, the components
other than the line cards). Use
if your router is in either a base configuration or a
redundant configuration.
Table 32: Chassis Power Consumption for Standard Configurations
Redundant Configuration
Base Configuration
Chassis Component
1100 W
1100 W
Fan tray
350 W/330 W
175 W/165 W
Routing and Control Board (128G/64G) at
40° C
1200 W
1000 W
Switch Fabric Board (SFB)
2650 W
2275 W
Total
98
Summary of Contents for MX10016
Page 1: ...MX10016 Universal Routing Platform Hardware Guide Published 2019 10 15 ...
Page 19: ......
Page 86: ......
Page 123: ......
Page 153: ......
Page 239: ...Figure 118 Moving the MX10016 Using a Mechanical Lift g100421 242 ...
Page 240: ...5 CHAPTER Troubleshooting Hardware Restoring Junos OS 245 Alarm Messages 249 ...
Page 241: ......
Page 249: ......
Page 277: ...Restricted Access Warning 281 ...
Page 292: ...Jewelry Removal Warning 296 ...
Page 295: ...Operating Temperature Warning 299 ...
Page 304: ...DC Power Disconnection Warning 308 ...
Page 308: ...DC Power Wiring Sequence Warning 312 ...
Page 311: ...DC Power Wiring Terminations Warning 315 ...
Page 320: ...Translation The emitted sound pressure is below 92 dB A per GR63 CORE 324 ...