Figure 28: JNP10K-PWR-DC2 Power Supply
g100595
CAUTION:
Do not mix power supplies models in the same chassis in a running
environment. DC and HVDC can coexist in the same chassis during the hot swap of DC
for HVDC.
To determine whether your system has the standard power bus or the enhanced power bus, see
.
WARNING:
The router is pluggable type A equipment installed in a restricted-access
location. It has a separate protective earthing terminal on the chassis that must be
connected to earth ground permanently to ground the chassis adequately and protect
the operator from electrical hazards.
CAUTION:
Before you begin installing the router, ensure that a licensed electrician has
attached an appropriate grounding lug to the grounding cable that you supply. Using a
grounding cable with an incorrectly attached lug can damage the router.
NOTE:
DC power supplies are shipped only in the redundant configuration of MX10016 routers.
For details about different chassis configurations, see
“MX10016 Components and Configurations”
.
JNP10K-PWR-DC2 models can use the standard bus or the enhanced bus. The enhanced bus supports
the full 5500 W available from the JNP10K-PWR-DC2. The standard bus provides 3000 W for power
67
Summary of Contents for MX10016
Page 1: ...MX10016 Universal Routing Platform Hardware Guide Published 2019 10 15 ...
Page 19: ......
Page 86: ......
Page 123: ......
Page 153: ......
Page 239: ...Figure 118 Moving the MX10016 Using a Mechanical Lift g100421 242 ...
Page 240: ...5 CHAPTER Troubleshooting Hardware Restoring Junos OS 245 Alarm Messages 249 ...
Page 241: ......
Page 249: ......
Page 277: ...Restricted Access Warning 281 ...
Page 292: ...Jewelry Removal Warning 296 ...
Page 295: ...Operating Temperature Warning 299 ...
Page 304: ...DC Power Disconnection Warning 308 ...
Page 308: ...DC Power Wiring Sequence Warning 312 ...
Page 311: ...DC Power Wiring Terminations Warning 315 ...
Page 320: ...Translation The emitted sound pressure is below 92 dB A per GR63 CORE 324 ...