A DC-powered device is equipped with a DC terminal block that is rated for the power requirements of
a maximally configured device.
NOTE:
To supply sufficient power, terminate the DC input wiring on a facility DC source that is
capable of supplying:
•
Minimum of 60 A at –48 VDC for MX10016 routers
Incorporate an easily accessible disconnect device into the facility wiring. Be sure to connect the ground
wire or conduit to a solid office earth ground. A closed loop ring is recommended for terminating the
ground conductor at the ground stud.
•
Run two wires from the circuit breaker box to a source of 48 VDC.
•
A DC-powered device that is equipped with a DC terminal block is intended only for installation in a
restricted-access location. In the United States, a restricted-access area is one in accordance with Articles
110-16, 110-17, and 110-18 of the National Electrical Code ANSI/NFPA 70.
NOTE:
Primary overcurrent protection is provided by the building circuit breaker. This breaker
must protect against excess currents, short circuits, and earth grounding faults in accordance
with NEC ANSI/NFPA 70.
•
Ensure that the polarity of the DC input wiring is correct. Under certain conditions, connections with
reversed polarity might trip the primary circuit breaker or damage the equipment.
•
For personal safety, connect the green and yellow wire to safety (earth) ground at both the device and
the supply side of the DC wiring.
•
The marked input voltage of –48 VDC for a DC-powered device is the nominal voltage associated with
the battery circuit, and any higher voltages are only to be associated with float voltages for the charging
function.
•
Because the device is a positive ground system, you must connect the positive lead to the terminal
labeled RTN, the negative lead to the terminal labeled –48 VDC, and the earth ground to the device
grounding points.
307
Summary of Contents for MX10016
Page 1: ...MX10016 Universal Routing Platform Hardware Guide Published 2019 10 15 ...
Page 19: ......
Page 86: ......
Page 123: ......
Page 153: ......
Page 239: ...Figure 118 Moving the MX10016 Using a Mechanical Lift g100421 242 ...
Page 240: ...5 CHAPTER Troubleshooting Hardware Restoring Junos OS 245 Alarm Messages 249 ...
Page 241: ......
Page 249: ......
Page 277: ...Restricted Access Warning 281 ...
Page 292: ...Jewelry Removal Warning 296 ...
Page 295: ...Operating Temperature Warning 299 ...
Page 304: ...DC Power Disconnection Warning 308 ...
Page 308: ...DC Power Wiring Sequence Warning 312 ...
Page 311: ...DC Power Wiring Terminations Warning 315 ...
Page 320: ...Translation The emitted sound pressure is below 92 dB A per GR63 CORE 324 ...