18 Technical data
70
18.3
Analog outputs of base unit and optional boards
18.4
Binary inputs base unit
18.5
Binary inputs optional boards
18.6
Binary outputs, power supply unit board
Signal type
Signal range
Admissible
load resistance
Accuracy
Effect of am-
bient tem-
perature
Voltage signal
0 to 10 V
> 500
Ω
≤
0.25 %
≤
100 ppm / K
Current signal
0/4 to 20 mA
< 450
Ω
≤
0.25 %
≤
100 ppm / K
Description
Input frequency
ranges
Min. pulse dura-
tion
Signal type
Switching thresh-
olds
a
a
This specification is relevant only if the Ext. voltage supply is selected under the “Contact” point in the
Configuration. Sensors and transmitters should be supplied from voltage supply outputs on the JUMO
AQUIS touch P. An externally supplied voltage signal must not have a voltage over 28 V.
On Off
On
Off
IN 1
b
b
All digital inputs IN 1 to 3 are suitable for connecting proximity switches. Recommended
types are: Wachendorff P2C2B1208NO3A2 and Balluff BES M12EG-PSC80F-BP03.
≤
1 Hz
300 ms
300 ms
Configurable as:
potential-free con-
tact,
or
ext. voltage supply
(maximal 28 V)
> 8 V
> 1.8 mA
< 5 V
< 1.2 mA
IN 2 to 3
b,c
Switching sig-
nal
c
Digital inputs IN 2 and IN 3 can be used for impeller flow-through sensors (water meters) or
magnetic-inductive flow-through meters (square-wave signal), for example. The input frequency depends
on the configured measuring principle in the flow-through function.
≤
1 Hz
30
μ
s
30
μ
s
IN 2 to 3
b,c
Flow
3 to 300 Hz
300 Hz
to
10 kHz
30
μ
s
30
μ
s
Max. number of retrofittable
digital inputs
Max.
pulse frequen-
cy
Min. pulse dura-
tion
Signal type
On Off
max. 2 optional boards with 3 digi-
tal inputs each
1 Hz
300 ms
300 ms
Potential-free contact
Description
Switching out-
put
Ampacity at ohm-
ic load
Contact life
a
a
The maximal ampacity of the contacts must not be exceeded.
OUT 1
Relay, change-
over contact
3 A at AC 250 V
150,000 switching cy-
cles
OUT 2
Relay, change-
over contact
Summary of Contents for 202580
Page 6: ...Content...
Page 28: ...12 Calibrating a pH measuring chain 28...
Page 42: ...15 Calibrating CR conductivity sensors 42...
Page 52: ...16 Calibrating Ci conductivity sensors 52...
Page 60: ...17 Calibrating universal inputs 60...
Page 79: ...79 18 Technical data...
Page 80: ...18 Technical data 80...
Page 81: ......