18 Technical data
18.2
Analog inputs optional boards
18.2.1
Universal input (IN 11, IN 12)
18.2.2
Analysis input: pH/Redox/NH
3
Probe-/Signal type
Connection type
Measuring
range
Measuring accu-
racy
Ambient
temperature
influence
Pt100 DIN EN 60751
2-wire/3-wire
-200 to +850 °C
≤
0.05% of MR
a
a
MR: measuring range span
≤
50 ppm/K
Pt1000 DIN EN 60751
2-wire/3-wire
-200 to +850 °C
≤
0.1% of MR
a
≤
50 ppm/K
Resistance transmitter/
Resistance potentiome-
ter
3-wire
100 to 4000
Ω
0.5% of R
Tot
b
b
R
Tot
: total resistance of the resistance transmitter/Resistance potentiometer
≤
100 ppm/K
RTD temperature probe
with
customer-specific char-
acteristic line
c
c
Customer-specific linearization can be used to enter a sensor characteristic line.
up to 400
Ω
2-wire/3-wire
0 to 400
Ω
≤
0.1% of R
max
d
d
R
max
: maximal resistance across the measuring range (400
Ω
or 4000
Ω
)
≤
100 ppm/K
to 4000
Ω
2-wire/3-wire
0 to 4000
Ω
≤
0.1% of R
max
d
≤
100 ppm/K
Voltage signal
-
0 to 10 V
0.2% of MR
a
100 ppm/K
Current signal
-
0(4) to 20 mA
0.1% of MR
a
100 ppm/K
Sensor lead resistance
e
e
Specification does not apply for standard signals
maximal 30
Ω
per line with 3-wire circuit
Lead calibration
e
Not required for 3-wire circuit. With a 2-wire circuit, lead calibration can
be executed at the respective input by means of an measured value cor-
rection with the aid of the "Offset" setting.
Measurand
Measuring range
Temperature
compensation
Measuring accu-
racy
Ambient
temperature
influence
pH-value
(standard electrode)
-2 to +16 pH
-10 to +150 °C
≤
0.3% of MR
a
a
MR: measuring range span
0.2%/10 K
pH-value
(ISFET electrode)
-2 to +16 pH
through
electrode
b
b
ISFET electrodes supply a temperature-compensated pH-measured value.
Redox voltage
-1500 to +1500 mV None
NH
3
(ammonia)
0 to 20000 ppm
-10 to +150 °C
Summary of Contents for 202580
Page 6: ...Content...
Page 28: ...12 Calibrating a pH measuring chain 28...
Page 42: ...15 Calibrating CR conductivity sensors 42...
Page 52: ...16 Calibrating Ci conductivity sensors 52...
Page 60: ...17 Calibrating universal inputs 60...
Page 79: ...79 18 Technical data...
Page 80: ...18 Technical data 80...
Page 81: ......