18 Technical data
64
18.1.2
Temperature measuring input (IN 5)
18.1.3
Universal input (IN 6)
18.1.4
Measuring circuit monitoring base unit
Probe-/Signal type
Connection type
Measuring
range
Measuring accu-
racy
Ambient
temperature
influence
Pt100 DIN EN 60751
2-wire/3-wire
-200 to +850 °C
≤
0.05% of MR
a
a
MR: measuring range span
≤
50 ppm/K
Pt1000 DIN EN 60751
2-wire/3-wire
-200 to +850 °C
≤
0.1% of MR
a
≤
50 ppm/K
Resistance transmitter/
Resistance potentiome-
ter
3-wire
0 to 100 k
Ω
0.5% of R
Tot
b
b
R
Tot
: total resistance of the resistance transmitter/Resistance potentiometer
≤
100 ppm/K
RTD temperature probe
with customer-specific
characteristic line
c
c
Customer-specific linearization can be used to enter a sensor characteristic line.
up to 400
Ω
2-wire/3-wire
0 to 400
Ω
≤
0.1% of R
max
d
d
R
max
: maximal resistance across the measuring range (400
Ω
,
4000
Ω
or 100 kW)
≤
100 ppm/K
to 4000
Ω
2-wire/3-wire
0 to 4000
Ω
to 100 k
Ω
2-wire/3-wire
0 to 100 k
Ω
NTC 8k55
2-wire/3-wire
0 to 150 °C
≤
0.1% of R
max
d
≤
100 ppm/K
NTC 22k
2-wire/3-wire
0 to 150 °C
Sensor lead resistance
maximal 30
Ω
per line with 3-wire circuit
Lead compensation
Not required for 3-wire circuit. With a 2-wire circuit, lead calibration can
be executed at the respective input by means of an measured value cor-
rection with the aid of the "Offset" setting.
Signal type
Measuring
range
Measuring accu-
racy
Ambient
temperature
influence
Current signal
0(4) to 20 mA
0.1% of MR
a
a
MR: measuring range span
100 ppm/K
Inputs
Underrange/
overrange
Temperature input
Yes
Universal input (current signal)
Yes
Summary of Contents for 202580
Page 6: ...Content...
Page 28: ...12 Calibrating a pH measuring chain 28...
Page 42: ...15 Calibrating CR conductivity sensors 42...
Page 52: ...16 Calibrating Ci conductivity sensors 52...
Page 60: ...17 Calibrating universal inputs 60...
Page 79: ...79 18 Technical data...
Page 80: ...18 Technical data 80...
Page 81: ......