JOHNSON CONTROLS
93
FORM 150.62-NM6 (103)
The TOTAL NUMbER OF COMPRESSORS is the total
quantity of compressors in the chiller, and determines
the stages of cooling available. Note in Table 21, the
chiller may have single or dual systems.
This MUST be programmed correctly
to assure proper chiller operation.
A single system chiller MUST have a
jumper between terminals 13 17 on
terminal block CTB1. If the jumper
is not installed, the unit will act as a
2system chiller. The jumper is only
checked by the micro at unit powerup.
If the jumper is removed, power must
be removed and reapplied to register
the change in memory.
The number of fans per system is programmed for the
total number of fans on each system, or the total number
on the chiller divided by 2. This is only programmable on
YCAL0090 - YCAL0124 chillers.
This MUST be programmed correctly
to assure proper chiller operation.
T O T A L N U M b E R O F
C O M P R E S S O R S = 6
2
N U M b E R O F F A N S
P E R S Y S T E M = x
460vAC SYSTEM TRIP vOLTS
For individual system high current trip programming on
460VAC chillers:
• Add the sum of the compressor and fan RLA’s in
the system
• Multiply the sum by 1.25
• Divide by 225A
• The resulting voltage is the value that should be
programmed
For example, if fan and compressor RLA’s total 100A:
5V x 100A
x 1.25 =
625VA
= 2.8V
225A
225A
The programmed value will be 2.8V. A similar calculation
and programming will be necessary for the other system
in a 2-system chiller.
460vAC UNIT TRIP vOLTS
For total chiller high current trip programming on 460VAC
chillers:
• Add the sum of all the the compressor and fan RLA’s
in the chiller
• Multiply the sum by 1.25
• Divide by 225A
• The resulting voltage is the value that should be
programmed
For example, if fan and compressor RLA’s total 180A:
5V x 180A
x 1.25 =
1125VA
= 5.0V
225A
225A
The programmed value will be 5.0V.
208/230vAC CHILLERS
On 208/230VAC chillers, the process is similar, but
instead of performing the calculation using 225A, a
number of 450A must be substituted.
When communications is required with a bAS or Op-
tiView Panel, individual unit IDs are necessary for com-
munications with specific chillers on a single RS-485
line. ID 0-7 is selectable.
S Y S x T R I P v O L T S
= x . x v O L T S
U N I T T R I P v O L T S
= x . x v O L T S
Depending on the option, the trip voltage for a
specific system or unit high current trip (See page
86) can be programmed. It also calibrates the current
readout under the OPER DATA key. The approximate
programmed value is calculated using the following
formulas:
R E M O T E U N I T I D
P R O G R A M M E D = x
Summary of Contents for York YCAL0014E Series
Page 111: ...JOHNSON CONTROLS 111 FORM 150 62 nm6 103 2 This page intentionally left blank...
Page 133: ...JOHNSON CONTROLS 133 FORM 150 62 nm6 103 4 LD08851...
Page 135: ...JOHNSON CONTROLS 135 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 137: ...JOHNSON CONTROLS 137 FORM 150 62 nm6 103 LD08855 4...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 62 nm6 103 LD08858 4...
Page 143: ...JOHNSON CONTROLS 143 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 62 nm6 103 LD08862 4...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 149: ...JOHNSON CONTROLS 149 FORM 150 62 nm6 103 LD08865...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 62 nm6 103 LD08867...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 62 nm6 103 LD08869...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 nm6 103 LD08872...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 62 nm6 103 4 LD08877...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 nm6 103 LD08874...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 nm6 103 This page intentionally left blank...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 62 nm6 103 4 LD08830...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 nm6 103 4 LD08833...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 nm6 103 4 LD08835...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 nm6 103 4 LD08837...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 nm6 103 4 LD08840...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 nm6 103 4 LD08842...
Page 179: ...JOHNSON CONTROLS 179 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 nm6 103 4 LD08844...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 nm6 103 4 LD08847...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 nm6 103 4 LD08849...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 nm6 103 4 This page intentionally left blank...