JOHNSON CONTROLS
13
FORM 150.62-NM6 (103)
EvAPORATOR PUMP START CONTACTS
Terminal block CTb2 – terminals 23 to 24, are nor mally-
open contacts that can be used to switch field supplied
power to provide a start signal to the evapo rator pump
contactor. The contacts will be closed when any of the
following conditions occur:
1. Low Leaving Chilled Liquid Fault
2. Any compressor is running
3. Daily schedule is not programmed OFF and the
Unit Switch is ON
The pump will not run if the micro panel has been pow-
ered up for less than 30 seconds, or if the pump has
run in the last 30 seconds, to prevent pump motor over-
heating. Refer to Figure 6 and unit wiring dia gram.
SYSTEM RUN CONTACTS
Contacts are available to monitor system status. Nor-
mally-open auxiliary contacts from each com pressor
contactor are wired in parallel with CTb2 – terminals
25 to 26 for system 1, and CTb2 – termi nals 27 to 28
for system 2 (YCAL0040 - YCAL0124). Refer to Figure
6 and unit wiring diagram.
ALARM STATUS CONTACTS
Normally-open contacts are available for each re frigerant
system. These normally-open contacts close when the
system is functioning normally. The respective contacts
will open when the unit is shut down on a unit fault, or
locked out on a system fault. Field connections are at
CTb2 terminals 29 to 30 (system 1), and terminals 31
to 32 (system 2 YCAL0040 - YCAL0124).
REMOTE START/STOP CONTACTS
To remotely start and stop the chiller, dry contacts can be
wired in series with the flow switch and CTB1 - termi nals
13 to 14. Refer to Figure 6 and unit wiring diagram.
REMOTE EMERGENCY CUTOFF
Immediate shutdown of the chiller can be accomplished
by opening a field-installed dry contact to break the elec-
trical circuit between terminals 5 to L on terminal block
CTb2. The unit is shipped with a factory jumper installed
between terminals 5 to L, which must be removed if
emergency shutdown contacts are installed. Refer to
Figure 6 and unit wiring diagram.
PwM INPUT
The PWM input allows reset of the chilled liquid set-
point by supplying a “timed” contact closure. Field wiring
should be connected to CTb1 – terminals 13 to 20. A
detailed explanation is provided in the Unit Control sec-
tion. Refer to Figure 6 and unit wiring diagram.
LOAD LIMIT INPUT
Load limiting is a feature that prevents the unit from
loading beyond a desired value. The unit can be “load
limited” either 33%, 40%, 50%, 66% or 80%, depending
on the number of compressors on unit. The field con
-
nections are wired to CTb1 – terminals 13 to 21, and
work in conjunction with the PWM inputs. A detailed
explanation is provided in the Unit Control section. Refer
to Figure 6 and unit wiring diagram.
When using the Load Limit feature,
the PWM feature will not function
– SIMULTANEOUS OPERATION
OF LOAD LIMITING AND TEM
PERATURE RESET (PWM INPUT)
CANNOT BE DONE.
FLOw SwITCH INPUT
The flow switch is field wired to CTB1 terminals 13 - 14.
See Figure 6 and unit wiring diagram.
COMPRESSOR HEATERS
Compressor heaters are standard. If power is OFF more
than two hours, the crankcase heaters must be ener-
gized for 18 - 24 hours prior to restarting a compressor.
This will assure that liquid slugging and oil dilution does
not damage the compressors on start.
1
Summary of Contents for York YCAL0014E Series
Page 111: ...JOHNSON CONTROLS 111 FORM 150 62 nm6 103 2 This page intentionally left blank...
Page 133: ...JOHNSON CONTROLS 133 FORM 150 62 nm6 103 4 LD08851...
Page 135: ...JOHNSON CONTROLS 135 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 137: ...JOHNSON CONTROLS 137 FORM 150 62 nm6 103 LD08855 4...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 62 nm6 103 LD08858 4...
Page 143: ...JOHNSON CONTROLS 143 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 62 nm6 103 LD08862 4...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 149: ...JOHNSON CONTROLS 149 FORM 150 62 nm6 103 LD08865...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 62 nm6 103 LD08867...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 62 nm6 103 LD08869...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 nm6 103 LD08872...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 62 nm6 103 4 LD08877...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 nm6 103 LD08874...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 nm6 103 This page intentionally left blank...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 62 nm6 103 4 LD08830...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 nm6 103 4 LD08833...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 nm6 103 4 LD08835...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 nm6 103 4 LD08837...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 nm6 103 4 LD08840...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 nm6 103 4 LD08842...
Page 179: ...JOHNSON CONTROLS 179 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 nm6 103 4 LD08844...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 nm6 103 4 LD08847...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 nm6 103 4 LD08849...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 nm6 103 4 This page intentionally left blank...