JOHNSON CONTROLS
99
FORM 150.62-NM6 (103)
Also see the UNIT KEYS PROGRAMMING qUICK
REFERENCE LIST in Table 23, Page 100.
CLOCK
The CLOCK display shows the current day, time, and
date. Pressing the CLOCK key will show the current
day, time, and date.
It is important that the date and time be correct, otherwise the
daily schedule will not function as desired if programmed. In
addition, for ease of troubleshooting via the History printouts,
the day, time, and date should be correct.
To change the day, time, and date press the CLOCK
key. The display will show something similar to the fol-
lowing:
The line under the F is the cursor. If the day is correct,
press the ENTER/ADV key. The cursor will move under
the 0 in 08 hours. If the day is incorrect, press the UP
or DOWN
arrow keys until the desired day is displayed
and then press the ENTER/ADV key at which time the
day will be accepted and the cursor will move under
the first digit of the “2 digit hour”. In a similar manner,
the hour, minute, meridian, month, day, and year may
be programmed, whenever the cursor is under the first
letter/numeral of the item. Press the UP or DOWN arrow
keys until the desired hour, minute, meridian, day, month,
and year are displayed. Pressing the ENTER/ADV Key
will save the valve and move the cursor on to the next
programmable variable.
Jumper J11 on the microboard must
be set to the “CLKON” position to turn
on the clock. If this is not done, the
clock will not function.
Option 13 – Unit Type:
The UNIT TYPE message cannot be modified under
the unit keys.
“LIqUID CHILLER” must be dis
played, or damage to compressors or
other components will occur if op
erated in the HEAT PUMP or CON
DENSING UNIT modes.
If unit type needs to be changed to make the unit a
liquid chiller, remove the jumper between J4-6 and
J4-11 and reapply power to the micropanel.
Option 14 – Refrigerant Type:
Refrigerant type R-22 or R-407C may be selected un-
der Service Mode. Refrigerant type is displayed under
the Options Key, but is only programmable in Service
Mode.
Incorrect programming may cause
damage to compressors.
Option 15 – Expansion valve Type:
Expansion valve type, thermostatic or electronic
may be selected under Service Mode. Expansion valve
type is displayed under the Options key, but is only pro-
grammable in Service Mode.
Incorrect programming may cause
damage to compressors.
2
U N I T T Y P E
L I Q U I D C H I L L E R
R E F R I G E R A N T T Y P E
R - 2 2
E x P A N S I O N v A L v E T Y P E
T H E R M O S T A T I C
T O D A Y I S F R I 0 8 : 5 1 A M
2 5 J A N 0 2
S O F T S T A R T
D I S A b L E D
This MUST be selected on all chillers without the soft
start option.
Summary of Contents for York YCAL0014E Series
Page 111: ...JOHNSON CONTROLS 111 FORM 150 62 nm6 103 2 This page intentionally left blank...
Page 133: ...JOHNSON CONTROLS 133 FORM 150 62 nm6 103 4 LD08851...
Page 135: ...JOHNSON CONTROLS 135 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 137: ...JOHNSON CONTROLS 137 FORM 150 62 nm6 103 LD08855 4...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 62 nm6 103 LD08858 4...
Page 143: ...JOHNSON CONTROLS 143 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 62 nm6 103 LD08862 4...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 149: ...JOHNSON CONTROLS 149 FORM 150 62 nm6 103 LD08865...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 62 nm6 103 LD08867...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 62 nm6 103 LD08869...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 nm6 103 LD08872...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 62 nm6 103 4 LD08877...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 nm6 103 LD08874...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 nm6 103 This page intentionally left blank...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 62 nm6 103 4 LD08830...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 nm6 103 4 LD08833...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 nm6 103 4 LD08835...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 nm6 103 4 LD08837...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 nm6 103 4 LD08840...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 nm6 103 4 LD08842...
Page 179: ...JOHNSON CONTROLS 179 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 nm6 103 4 LD08844...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 nm6 103 4 LD08847...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 nm6 103 4 LD08849...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 nm6 103 4 This page intentionally left blank...