JOHNSON CONTROLS
120
FORM 150.62-NM6 (103)
Service and Troubleshooting
Entering Chilled Liquid Sensor
J6-6 = +5VDC regulated supply to sensor.
J6-9 = VDC input signal to the microboard.
See Table 38 for voltage readings that
correspond to specific liquid temperatures.
J6-3 = drain (shield connection = 0VDC)
Leaving Chilled Liquid Temp. Sensor
J6-5 = +5VDC regulated supply to sensor.
J6-8 = VDC input signal to the microboard.
See Table 38 for voltage readings that
correspond to specific liquid temperatures.
J6-2 = drain (shield connection = 0VDC)
Cooler Inlet Temperature
J5-12 = VDC input signal to microboard from Sys 1
Cooler Inlet Refrigerant Temp Sensor (R-407c
only).
J5-13 = VDC input signal to microboard from Sys 2
Cooler Inlet Refrigerant Temp Sensor (R-407c
only).
Suction Temp Sensor
J5-14 = VDC input signal to microboard from Sys 1
Suction Temp Sensor (EEV only).
J5-15 = VDC input signal to microboard from Sys 2
Suction Temp Sensor (EEV only).
TEMP °F
vOLTAGE
RESISTANCE
TEMP °C
0
1.71
25619
-18
2
1.78
24046
-17
4
1.85
22580
-16
6
1.93
21214
-14
8
2.00
19939
-13
10
2.07
18749
-12
12
2.15
17637
-11
14
2.22
16599
-10
16
2.30
15629
-9
18
2.37
14721
-8
20
2.45
13872
-7
22
2.52
13077
-6
24
2.59
12333
-4
26
2.67
11636
-3
28
2.74
10982
-2
30
2.81
10370
-1
32
2.88
9795
0
34
2.95
9256
1
36
3.02
8750
2
38
3.08
8276
3
40
3.15
7830
4
42
3.21
7411
6
44
3.27
7017
7
46
3.33
6647
8
48
3.39
6298
9
50
3.45
5970
10
52
3.51
5661
11
54
3.56
5370
12
56
3.61
5096
13
58
3.67
4837
14
60
3.72
4593
16
62
3.76
4363
17
64
3.81
4145
18
66
3.86
3941
19
68
3.90
3747
20
70
3.94
3564
21
72
3.98
3392
22
74
4.02
3228
23
76
4.06
3074
24
78
4.10
2928
26
80
4.13
2790
27
TAbLE 38 –
ENTERING/LEAVING CHILLED
LIqUID TEMP. SENSOR, COOLER IN-
LET TEMPERATURE SENSOR, AND
SUCTION TEMPERATURE SENSOR:
TEMPERATURE/VOLTAGE/RESISTANCE
CORRELATION
Summary of Contents for York YCAL0014E Series
Page 111: ...JOHNSON CONTROLS 111 FORM 150 62 nm6 103 2 This page intentionally left blank...
Page 133: ...JOHNSON CONTROLS 133 FORM 150 62 nm6 103 4 LD08851...
Page 135: ...JOHNSON CONTROLS 135 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 137: ...JOHNSON CONTROLS 137 FORM 150 62 nm6 103 LD08855 4...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 62 nm6 103 LD08858 4...
Page 143: ...JOHNSON CONTROLS 143 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 62 nm6 103 LD08862 4...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 149: ...JOHNSON CONTROLS 149 FORM 150 62 nm6 103 LD08865...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 62 nm6 103 LD08867...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 62 nm6 103 LD08869...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 nm6 103 LD08872...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 62 nm6 103 4 LD08877...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 nm6 103 LD08874...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 nm6 103 This page intentionally left blank...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 62 nm6 103 4 LD08830...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 nm6 103 4 LD08833...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 nm6 103 4 LD08835...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 nm6 103 4 LD08837...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 nm6 103 4 LD08840...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 nm6 103 4 LD08842...
Page 179: ...JOHNSON CONTROLS 179 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 nm6 103 4 LD08844...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 nm6 103 4 LD08847...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 nm6 103 4 LD08849...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 nm6 103 4 This page intentionally left blank...