CONDENSER FAN CONTROL - YCAL0014 – YCAL0080
TAbLE 27 –
YCAL0014 – YCAL0080 CONDENSER FAN CONTROL USING OUTDOOR AMbIENT TEMPERA-
TURE AND DISCHARGE PRESSURE (DISCHARGE PRESSURE CONTROLS WILL NOT FUNC-
TION UNLESS THE OPTIONAL DISCHARGE PRESSURE TRANSDUCER IS INSTALLED)
CONTACTOR
MICRO BOARD
FAN #
FAN STAGE
ON
OFF
OUTPUT TB-4
SYS 1 SYS 2
SYS 1 SYS 2
SYS 1 SYS 2
1
OAT >25°F (-3.9°C)
OAT < 20°F (-6.7°C)
1 FAN FWD
OR
AND
8M 11M
4 8
3 4
DP > Fan Ctrl On Press
DP < Fan Ctrl On Press – (Diff. Press.)
*3
OAT >65°F (18.3°C)
OAT < 60°F (15.6°C)
2 FAN FWD
OR
AND
7M & 10M &
2 & 4 6 & 8
1 & 3 2 & 4
DP > Fan Ctrl On Press
DP < Fan Ctrl On Press –
8M
11M
+ 40 PSIG (2.76 Bars)
[Diff. Press + 40 PSIG (2.76 Bars)]
TAbLE 28 –
YCAL0014 – YCAL0080 CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY
CONTACTOR
MICRO BOARD
FAN #
FAN STAGE
ON
OFF
OUTPUT TB-4
SYS 1 SYS 2
SYS 1 SYS 2
SYS 1 SYS 2
1
DP > Fan Ctrl On Press DP < Fan Ctrl On Press – (Diff. Press.)
8M 11M
4 8
3 4
1 FAN FWD
*3
DP > Fan Ctrl On Press +
DP < Fan Ctrl On Press –
7M & 10M &
2 & 4 6 & 8
1 & 3 2 & 4
2 FANS FWD
40 PSIG (2.76 Bars)
[(Diff. Press.) + 40 PSIG (2.76 Bars)]
8M
11M
* NOTE:
STEP 2 is not active in the “Standard Ambient” mode. When changing to “Low Ambient” control, fan power wiring also changes.
Summary of Contents for York YCAL0014E Series
Page 111: ...JOHNSON CONTROLS 111 FORM 150 62 nm6 103 2 This page intentionally left blank...
Page 133: ...JOHNSON CONTROLS 133 FORM 150 62 nm6 103 4 LD08851...
Page 135: ...JOHNSON CONTROLS 135 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 137: ...JOHNSON CONTROLS 137 FORM 150 62 nm6 103 LD08855 4...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 62 nm6 103 LD08858 4...
Page 143: ...JOHNSON CONTROLS 143 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 62 nm6 103 LD08862 4...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 149: ...JOHNSON CONTROLS 149 FORM 150 62 nm6 103 LD08865...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 62 nm6 103 LD08867...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 62 nm6 103 LD08869...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 nm6 103 LD08872...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 62 nm6 103 4 LD08877...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 nm6 103 LD08874...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 nm6 103 This page intentionally left blank...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 62 nm6 103 4 LD08830...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 nm6 103 4 LD08833...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 nm6 103 4 LD08835...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 nm6 103 4 LD08837...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 nm6 103 4 LD08840...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 nm6 103 4 LD08842...
Page 179: ...JOHNSON CONTROLS 179 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 nm6 103 4 LD08844...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 nm6 103 4 LD08847...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 nm6 103 4 LD08849...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 nm6 103 4 This page intentionally left blank...