JOHNSON CONTROLS
70
FORM 150.62-NM6 (103)
UNIT CONTROLS
YORK MILLENNIUM CONTROL CENTER
The YORK MicroComputer Control Center is a micro-
processor based control system designed to provide
the entire control for the liquid chiller. The control logic
embedded in the microprocessor based control system
will provide control for the chilled liquid temperatures, as
well as sequencing, system safeties, displaying status,
and daily schedules. The MicroComputer Control Center
consists of four basic components, 1) microprocessor
board, 2) transformer, 3) display and 4) keypad. The
keypad allows programming and accessing setpoints,
pressures, temperatures, cutouts, daily schedule, op-
tions, and fault information.
Remote cycling, demand limiting and chilled liquid tem-
perature reset can be accomplished by field supplied
contacts.
Compressor starting/stopping and loading/unloading
decisions are performed by the Microprocessor to
maintain leaving or return chilled liquid temperature.
These decisions are a function of temperature devia-
tion from setpoint.
A Master ON/Off switch is available to activate or deac-
tivate the unit.
INTRODUCTION
MICROPROCESSOR bOARD
The Microprocessor board is the controller and de-
cision maker in the control panel. System inputs such
as pressure transducers and temperature sensors are
connected directly to the Microprocessor board. The
Microprocessor board circuitry multiplexes the analog
inputs, digitizes them, and scans them to keep a con-
stant watch on the chiller operating conditions. From this
information, the Microprocessor then issues commands
to the Relay Outputs to control contactors, solenoids,
etc. for Chilled Liquid Temperature Control and to react
to safety conditions.
Keypad commands are acted upon by the micro to
change setpoints, cutouts, scheduling, operating re-
quirements, and to provide displays.
The on-board power supply converts 24VAC from the 1T
transformer to a +12VDC and +5VDC regulated supply
located on the Microprocessor board. This voltage is
used to operate integrated circuitry on the board. The 40
character display and unit sensors are supplied power
from the microboard 5VDC supply.
24VAC is rectified and filtered to provide unregulated
+30VDC to supply the flow switch, PWM remote tem
-
perature reset, and demand limit circuitry which is avail-
able to be used with field supplied contacts.
00065VIP
Unit Controls
Summary of Contents for York YCAL0014E Series
Page 111: ...JOHNSON CONTROLS 111 FORM 150 62 nm6 103 2 This page intentionally left blank...
Page 133: ...JOHNSON CONTROLS 133 FORM 150 62 nm6 103 4 LD08851...
Page 135: ...JOHNSON CONTROLS 135 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 137: ...JOHNSON CONTROLS 137 FORM 150 62 nm6 103 LD08855 4...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 62 nm6 103 LD08858 4...
Page 143: ...JOHNSON CONTROLS 143 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 62 nm6 103 LD08862 4...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 149: ...JOHNSON CONTROLS 149 FORM 150 62 nm6 103 LD08865...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 62 nm6 103 LD08867...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 62 nm6 103 LD08869...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 nm6 103 LD08872...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 62 nm6 103 4 LD08877...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 nm6 103 LD08874...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 nm6 103 This page intentionally left blank...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 62 nm6 103 4 LD08830...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 nm6 103 4 LD08833...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 nm6 103 4 LD08835...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 nm6 103 4 LD08837...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 nm6 103 4 LD08840...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 nm6 103 4 LD08842...
Page 179: ...JOHNSON CONTROLS 179 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 nm6 103 4 LD08844...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 nm6 103 4 LD08847...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 nm6 103 4 LD08849...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 nm6 103 4 This page intentionally left blank...