JOHNSON CONTROLS
91
FORM 150.62-NM6 (103)
SETPOINT KEY
MODE
LOw LIMIT
HIGH LIMIT
DEFAULT
LEAVING CHILLED LIqUID SETPOINT
WATER COOLING
40.0°F
**70.0°F 44.0°F
4.4°C
21.1°C
6.7°C
GLYCOL COOLING
*10.0°F
**70.0°F
44.0°F
-12.2°C
21.1°C
6.7°C
LEAVING CHILLED LIqUID
—
1.5°F
2.5°F
2.0°F
CONTROL RANGE
0.8
°C
1.4°C
1.1°C
RETURNED CHILLED LIqUID SETPOINT
WATER COOLING
40.0°F
70.0°F
44.0°F
4.4°C
21.1°C
6.7°C
GLYCOL COOLING
10.0°F
70.0°F
44.0°F
-12.2°C
21.1°C
6.7°C
RETURN CHILLED LIqUID
—
4.0°F
20.0°F
10.0°F
CONTROL RANGE
2.2°C
11.1°C
5.6°C
MAx EMS-PWM REMOTE
—
2°F
40°F
20°F
TEMPERATURE RESET
1.0°C
22.0°C
11.0°C
*
Refer to Engineering Guide for operation below 30°F (-1.1°C). Alternate thermal expansion valves must be used
below 30°F (-1.1°C).
*
When using glycol, Leaving Chilled Liquid Setpoint should not be set below 20°F (-6.7°C).
** Do not exceed 55°F (12.8°C) setpoint before contacting the nearest YORK
Office for application
guidelines.
TAbLE 20 –
COOLING SETPOINTS, PROGRAMMAbLE LIMITS AND DEFAULTS
2
box. The operation is then repeated if necessary. This
process may be followed until the hour, minutes, and
meridian (AM or PM) of both the START and STOP
points are set. After changing the meridian of the stop
time, pressing the ENTER/ADV key will advance the
schedule to the next day.
Whenever the daily schedule is
changed for Monday, all the other
days will change to the new Monday
schedule. This means if the Monday
times are not applicable for the whole
week then the exceptional days would
need to be reprogrammed to the de
sired schedule.
To page to a specific day press the SCHEDULE/
ADVANCE DAY
key. The start and stop time of each
day may be programmed differently using the UP and
DOWN arrow, and ENTER/ADV keys.
After SUN (Sunday) schedule appears on the display a
subsequent press of the SCHEDULE/ADVANCE DAY
key will display the Holiday schedule. This is a two part
display. The first reads:
The times may be set using the same procedure
as described above for the days of the week. After
changing the meridian of the stop time, pressing the
ENTER/ADV key will advance the schedule to the
following display:
The line below the empty space next to the S is the
cursor and will move to the next empty space when the
ENTER/ADV key is pressed. To set the Holiday, the
cursor is moved to the space following the day of the
week of the holiday and the UP arrow key is pressed.
An * will appear in the space signifying that day as a
holiday. The * can be removed by pressing the DOWN
arrow key.
The Holiday schedule must be programmed weekly
–once the Holiday schedule runs, it will revert to the
normal daily schedule.
PROGRAM key
There are several operating parameters under the PRO-
GRAM key that are programmable. These setpoints can
be changed by pressing the PROGRAM key, and then
the ENTER/ADV key to enter
Program Mode
. Continuing
to press the ENTER/ADV key will display each oper-
ating parameter. While a particular parameter is being
displayed, the UP and DOWN arrow keys can be used
H O L S T A R T = 0 0 : 0 0 A M
S
T
O
P = 0
0 : 0
0 A
M
S _ M T w T F S
H O L I D A Y N O T E D b Y *
Summary of Contents for York YCAL0014E Series
Page 111: ...JOHNSON CONTROLS 111 FORM 150 62 nm6 103 2 This page intentionally left blank...
Page 133: ...JOHNSON CONTROLS 133 FORM 150 62 nm6 103 4 LD08851...
Page 135: ...JOHNSON CONTROLS 135 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 137: ...JOHNSON CONTROLS 137 FORM 150 62 nm6 103 LD08855 4...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 62 nm6 103 LD08858 4...
Page 143: ...JOHNSON CONTROLS 143 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 62 nm6 103 LD08862 4...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 149: ...JOHNSON CONTROLS 149 FORM 150 62 nm6 103 LD08865...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 62 nm6 103 LD08867...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 62 nm6 103 LD08869...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 nm6 103 LD08872...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 62 nm6 103 4 LD08877...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 nm6 103 LD08874...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 nm6 103 This page intentionally left blank...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 62 nm6 103 4 LD08830...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 nm6 103 4 LD08833...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 nm6 103 4 LD08835...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 nm6 103 4 LD08837...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 nm6 103 4 LD08840...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 nm6 103 4 LD08842...
Page 179: ...JOHNSON CONTROLS 179 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 nm6 103 4 LD08844...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 nm6 103 4 LD08847...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 nm6 103 4 LD08849...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 nm6 103 4 This page intentionally left blank...