As an example of compressor staging (refer to Table 34),
a chiller with six compressors using a Cooling Setpoint
programmed for 45°F (7.20°C) and a Range Setpoint
of 10°F (5.56°C). Using the formulas in Table 25, the
control range will be split up into six (seven including
hot gas) segments, with the Control Range determining
the separation between segments. Note also that the
Cooling Setpoint is the point at which all compressors
are off, and Cooling Setpoint plus Range is the point
all compressors are on. Specifically, if the return water
temperature is 55°F (12.8°C), then all compressors
will be on, providing full capacity. At nominal gpm, this
would provide approximately 45°F (7.2°C) leaving water
temperature out of the evaporator.
If the return water temperature drops to 53.4°F (11.9°C),
one compressor would cycle off leaving five compres
-
sors running. The compressors would continue to cycle
off approximately every 1.7°F (.94°C), with the exception
of hot gas bypass. Notice that the hot gas bypass would
be available when the return water temperature dropped
to 46.25°F (7.9°C). At this point one compressor would
be running.
Should the return water temperature rise from this point
to 46.7°F (8.2°C), the hot gas bypass would shut off, still
leaving one compressor running. As the load increased,
the compressors would stage on every 1.7°F (.94°C).
Also notice that Tables 24, 25 and 26 not only provide
the formulas for the loading (ON POINT) and unloading
(OFF POINT) of the system, the “STEP” is also shown
in the tables. The “STEP” is that sequence in the ca-
pacity control scheme that can be viewed under the
OPER DATA key. Please refer to the section on the
DISPLAY/PRINT keys for specific information on the
OPER DATA key.
TAbLE 24 –
COMPRESSOR STAGING FOR RETURN WATER CONTROL
*Unloading only
COMPRESSOR STAGING FOR RETURN wATER CONTROL
6 COMPRESSORS
COOLING SETPOINT = 45°F (7.2°C) RANGE = 10°F (5.6°C)
# OF COMP ON
0
*1+HG
1
2
3
4
5
6
RWT
45°F
46.25°F 46.7°F 48.3°F 50.0°F 51.7°F 53.4°F
55.0°F
(7.2°C)
(7.9°C) (8.2°C) (9.1°C) (10.0°C)
(11.0°C)
(11.9°C)
(12.8°C)
TAbLE 25 –
RETURN CHILLED LIqUID CONTROL FOR 5 & 6 COMPRESSORS (7 & 8 STEPS)
*STEP
COMPRESSOR
COMPRESSOR ON POINT
COMPRESSOR OFF POINT
0
0
SETPOINT
SETPOINT
1
1 W/HGb
SP + CR/8 (Note 1)
SETPOINT
2
1 NO HGb
SP + CR/6
SETPOINT
3
2
SP + 2*CR/6 (Note 2)
SP + CR/6
4
2
SP + 2*CR/6
SP + CR/6
(Note 3)
5
3
SP + 3*CR/6
SP + 2*CR/6
6
4
SP + 4*CR/6
SP + 3*CR/6
7**
5
SP + 5*CR/6
SP + 4*CR/6
8
6
SP + CR
SP + 5*CR/6
NOTES:
1. Step 1 is Hot Gas bypass and is skipped when loading occurs. Hot Gas bypass operation is inhibited during Pumpdown.
2. Step 3 is skipped when loading occurs.
3. Step 4 is skipped when unloading occurs.
*
STEP can be viewed using the OPER DATA key and scrolling to COOLING DEMAND.
** 5-Compressor Chillers stop at 7 steps
Summary of Contents for York YCAL0014E Series
Page 111: ...JOHNSON CONTROLS 111 FORM 150 62 nm6 103 2 This page intentionally left blank...
Page 133: ...JOHNSON CONTROLS 133 FORM 150 62 nm6 103 4 LD08851...
Page 135: ...JOHNSON CONTROLS 135 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 137: ...JOHNSON CONTROLS 137 FORM 150 62 nm6 103 LD08855 4...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 62 nm6 103 LD08858 4...
Page 143: ...JOHNSON CONTROLS 143 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 62 nm6 103 LD08862 4...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 149: ...JOHNSON CONTROLS 149 FORM 150 62 nm6 103 LD08865...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 62 nm6 103 LD08867...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 62 nm6 103 LD08869...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 nm6 103 LD08872...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 62 nm6 103 4 LD08877...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 nm6 103 LD08874...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 nm6 103 This page intentionally left blank...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 62 nm6 103 4 LD08830...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 nm6 103 4 LD08833...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 nm6 103 4 LD08835...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 nm6 103 4 LD08837...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 nm6 103 4 LD08840...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 nm6 103 4 LD08842...
Page 179: ...JOHNSON CONTROLS 179 FORM 150 62 nm6 103 4 This page intentionally left blank...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 nm6 103 4 LD08844...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 nm6 103 4 LD08847...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 nm6 103 4 LD08849...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 nm6 103 4 This page intentionally left blank...