JOHNSON CONTROLS
87
SECTION 6 - TECHNICAL DATA
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
6
STANDARD EFFICIENCY 3-COMPRESSOR UNITS (CONT'D)
(One Field Provided Power Supply Circuit. Field Connections to Factory provid-
ed Terminal Block (Standard); or Individual System Breakers (Optional).
YCIV
S/P
CON-
TROL
KVA (7)
UNIT SHORT CIRCUIT
WITHSTAND (KA)
FIELD WIRING & PROTECTION
FIELD WIRING & PROTECTION
FIELD WIRING LUGS
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/HIGH
STATIC FANS
HIGH HEAD/HIGH
STATIC FANS
TWO-SPEED
COND. FANS
STD TERMINAL
BLOCK
OPT CIRCUIT
BREAKER
TERMINAL
BLOCK
(STD)
CIRCUIT
BREAK-
ER (OPT)
MINIMUM
CKT.
AMPACITY
(MCA) (3)
RECOMMEND-
ED FUSE/CKT.
BREAKER RAT-
ING (4)
MAX. IN-
VERSE
TIME
CKT.
BRKR.
RATING
(2)
MAX
DUAL
ELEMENT
FUSE
SIZE (2)
MINIMUM
CKT.
AMPACITY
(MCA) (3)
RECOMMENDED
FUSE/CKT.
BREAKER RAT-
ING (4)
MAX.
INVERSE
TIME CKT.
BRKR.
RATING
(2)
MAX
DUAL
ELEMENT
FUSE
SIZE (2)
MINIMUM
CKT.
AMPACITY
(MCA) (3)
RECOMMENDED
FUSE/CKT.
BREAKER RAT-
ING (4)
MAX.
INVERSE
TIME CKT.
BRKR.
RATING
(2)
MAX
DUAL
ELEMENT
FUSE
SIZE (2)
LUGS/
PHASE
(1)
LUG
WIRE
RANGE
LUGS/
PHASE
(1)
LUG
WIRE
RANGE
0287
2.4
30KA
65KA
494
600
600
600
4
#2 - 600
KCM
4
#4/0 -
500 KCM
2.4
30KA
65KA
624
700
800
800
676
800
800
800
4
#2 - 600
KCM
4
#4/0 -
500 KCM
0307
2.4
30KA
65KA
540
600
700
700
4
#2 - 600
KCM
4
#4/0 -
500 KCM
2.4
30KA
65KA
682
800
800
800
731
800
800
800
4
#2 - 600
KCM
4
#4/0 -
500 KCM
0357
2.4
30KA
65KA
607
700
800
800
4
#2 - 600
KCM
4
#4/0 -
500 KCM
2.4
30KA
65KA
766
1000
1000
1000
827
1000
1000
1000
4
#2 - 600
KCM
4
#4/0 -
500 KCM
0397
2.4
30KA
65KA
671
800
800
800
4
#2 - 600
KCM
4
#4/0 -
500 KCM
2.4
30KA
65KA
847
1000
1000
1000
911
1000
1000
1000
4
#2 - 600
KCM
4
#4/0 -
500 KCM
See page 92 for Electrical Data footnotes.
MODEL NO./NAME-
PLATE
SYSTEM 1
SYSTEM 2
SYSTEM 2
SYSTEM 3
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED
COND. FANS
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED
COND. FANS
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED
COND. FANS
YCIV
S/P
INPUT
VOLTS
(9)
INPUT
FREQ
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENS-
ER FANS
COMP. CONDENS-
ER FANS
COMP. CONDENS-
ER FANS
COMP. CONDENS-
ER FANS
COMP. CONDENS-
ER FANS
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
0287
460
60
146
5
2.8
164
4
2.8
108
4
2.8
380
60
184
5
3.5
184
5
9.3
207
4
3.5
207
4
9.3
136
4
3.5
136
4
9.3
0307
460
60
147
5
2.8
147
5
2.8
165
4
2.8
380
60
186
5
3.5
186
5
9.3
186
5
3.5
186
5
9.3
208
4
3.5
208
4
9.3
0357
460
60
160
5
2.8
160
5
2.8
193
6
2.8
380
60
202
5
3.5
202
5
9.3
202
5
3.5
202
5
9.3
244
6
3.5
244
6
9.3
0397
460
60
191
6
2.8
191
6
2.8
191
6
2.8
380
60
241
6
3.5
241
6
9.3
241
6
3.5
241
6
9.3
241
6
3.5
241
6
9.3
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...