JOHNSON CONTROLS
323
SECTION 9 - MAINTENANCE
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
9
TABLE 35 -
COMPRESSOR MOTOR OVERLOAD SETTINGS AND MAX. VSD FREQUENCY
2 COMP CHILLER MODELS WITH STANDARD (PIN 52 = X) AND ULTRA QUIET FANS (PIN 52 = L)
CHILLER MODEL
(2 COMP)
W/ STD & UQ FANS
CHILLER NAME-
PLATE VOLTAGE
(VAC)
COMPRESSOR 1
OVERLOAD SETTING
(AMPS)
COMPRESSOR 2
OVERLOAD SETTING
(AMPS)
MAXIMUM VSD FRE-
QUENCY (HZ)
YCIV0157EA/VA
380
269
269
186
YCIV0157EA/VA
460
192
192
186
YCIV0157SA/PA
380
273
273
200
YCIV0157SA/PA
460
196
196
200
YCIV0177EA/VA
380
262
275
200
YCIV0177EA/VA
460
184
197
200
YCIV0177SA/PA
380
289
267
182
YCIV0177SA/PA
460
270
191
182
YCIV0187EA/VA
380
289
259
192
YCIV0187EA/VA
460
250
183
192
YCIV0187SA/PA
380
289
275
200
YCIV0187SA/PA
460
254
198
200
YCIV0197EA/VA
380
289
289
182
YCIV0197EA/VA
460
244
244
182
YCIV0207EA/VA
380
289
289
192
YCIV0207EA/VA
460
234
250
192
YCIV0207SA/PA
380
289
289
186
YCIV0207SA/PA
460
247
273
186
YCIV0227EA/VA
380
289
289
200
YCIV0227EA/VA
460
238
238
200
YCIV0227SA/PA
380
289
289
200
YCIV0227SA/PA
460
255
255
200
YCIV0247EA/VA
380
345
314
200
YCIV0247EA/VA
460
289
238
200
YCIV0247SA/PA
380
345
331
200
YCIV0247SA/PA
460
289
254
200
YCIV0267SA/PA
380
345
345
200
YCIV0267SA/PA
460
289
289
200
NOTE:
Overload settings are based on Chiller Model and Condenser Fan Option
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...