SECTION 8 - MICROPANEL
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
8
BACnet and Modbus Communications
Chiller data that can be read and modified using spe-
cific BACnet or Modbus Register Addresses; and the
data associated with the addresses, is outlined in the
following description:
ANALOG WRITE POINTS
This data can be read and modified using a BACnet
or Modbus network connection. The Modbus Register
Address for these points is 1025 plus AV #.
BINARY WRITE POINTS
This data can be read and modified using a BACnet
or Modbus network connection. The Modbus Register
Address for these points is 1537 plus BV #.
ANALOG READ ONLY POINTS
This data can be read using a BACnet or Modbus net-
work connection and can NOT be modified using this
connection. The Modbus Register Address for these
points is 513 plus AI #.
BINARY MONITOR ONLY POINTS
This data can be read using a BACnet or Modbus net-
work connection and can NOT be modified using this
connection. The Modbus Register Address for these
points is 1281 plus BI #.
Refer to
for complete list of
BACnet and Modbus registers.
The latest data map information is listed
on the Johnson Controls Equipment In-
tegration website.
Communications Data Map Notes
1.
IPU II based units are configured for Native BAC
-
net MS/TP and Modbus RTU communications.
Microgateway or E-Link not required for these
two communication protocols.
2.
BACnet Object Types: 0= Analog In, 1 =
Analog Out, 2= Analog Value, 3= Bina-
ry In, 4 = Binary Output, 5= Binary Value,
8= Device, 15 = Alarm Notification (0
through
127 are reserved ASHRAE Objects).
3. WC= Inches of water column; CFM = Cubic Feet
per Minute; FPM = Feet per Minute: PSI = Lbs
per square inch; Pa = Pascals; kPa = Kilopascals;
PPM = Part per Million; kJ/kg = Kilojoules per
Kilogram.
4.
Water Cooled Scroll units use the same firmware
as Air-Cooled Scroll units, ignoring Fan Control.
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...