![Johnson Controls YCIV0157 Installation Operation & Maintenance Download Page 72](http://html1.mh-extra.com/html/johnson-controls/yciv0157/yciv0157_installation-operation-and-maintenance_2023452072.webp)
JOHNSON CONTROLS
72
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
SECTION 6 - TECHNICAL DATA
PHYSICAL DATA (SI - STANDARD EFFICIENCY)
REFRIGERANT R-134A
STANDARD EFFICIENCY
MODEL NUMBER (YCIV____ S/P)
GENERAL UNIT DATA
60HZ
0157
0177
0187
0207
0227
0247
0267
Number of Independent Refrigerant Circuits
2
2
2
2
2
2
2
Refrigerant Charge, R-134a, Ckt.-1/Ckt.-2, kg.
74/74
77/77
84/77
87/80
87/87
105/89
105/105
Oil Charge, Ckt.-1/Ckt.-2, liters
19/19
19/19
19/19
19/19
19/19
19/19
19/19
Compressors, Semihermetic Screw Qty per
Chiller
2
2
2
2
2
2
2
Condensers, High Efficiency Fin/Tube with Integral Subcooler
Total Chiller Coil Face Area, m2
21.8
21.8
24.5
24.5
27.2
30.0
32.7
Number of Rows
3
3
3
3
3
3
3
Fins per meter
669
669
669
669
669
669
669
Condenser Fans
Number, Ckt.-1/Ckt.-2
4/4
4/4
5/4
5/4
5/5
6/5
6/6
Low Noise Fans
Fan Motor, HP/kWi
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
Total Chiller Airflow, l/sec.
49082
49082
55218
55218
61353
67488
73624
Ultra Quiet Fans
Fan Motor, HP/kWi
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
Total Chiller Airflow, l/sec.
49082
49082
55218
55218
61353
67488
73624
Dual Speed Fans - Normal Speed
Fan, KWi
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Total Chiller, m3/s
42
42
47
47
52
57
62
Dual Speed Fans - Lower Speed
Fan, KWi
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Total Chiller, m3/s
32
32
36
36
40
44
48
High Static Fans
Fan, KWi
3.7
3.7
3.7
3.7
3.7
3.7
3.7
Total Chiller, m3/s
49
49
55
55
61
67
74
Evaporator, Direct Expansion
Water Volume, liters
253.6
359.6
359.6
529.9
529.9
529.9
529.9
Maximum Water Side Pressure, Bar
10
10
10
10
10
10
10
Maximum Refrigerant Side Pressure, Bar
16
16
16
16
16
16
16
Minimum Chilled Water Flow Rate, l/sec.
8.8
10.1
10.1
11.4
11.4
11.4
11.4
Maximum Chilled Water Flow Rate, l/sec.
42.6
47.3
47.3
50.5
50.5
50.5
50.5
Water Connections, inches
8
10
10
10
10
10
10
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...