SECTION 6 - TECHNICAL DATA
HIGH EFFICIENCY 2-COMPRESSOR UNITS
One Field Provided Power Supply Circuit. Field Connections to Factory provided
Terminal Block (Standard); or Individual System Breakers (Optional).
HIGH EFFICIENCY YCIV_ _ _ _ E/V
HIGH EFFICIENCY YCIV_ _ _ _ E/V
MODEL NO./NAME-
PLATE
SYSTEM 1
SYSTEM 2
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED
COND. FANS
STD. & ULTRA QUIET COND. FANS
HIGH HEAD/STATIC COND. FANS
TWO-SPEED COND. FANS
YCIV
E/V
INPUT
VOLTS
(9)
INPUT
FREQ
COMPRESSOR CONDENSER
FANS
COMPRESSOR CONDENSER
FANS
COMPRESSOR CONDENSER
FANS
COMPRESSOR
CONDENSER
FANS
COMPRESSOR
CONDENSER
FANS
COMPRESSOR
CONDENSER
FANS
RLA (5)
QTY.
FLA
(EA)
RLA (5)
QTY.
FLA
(EA)
RLA (5)
QTY.
FLA
(EA)
RLA (5)
QTY.
FLA
(EA)
RLA (5)
QTY.
FLA
(EA)
RLA (5)
QTY.
FLA
(EA)
0157
460
60
110
4
2.8
110
4
2.8
380
60
139
4
3.5
139
4
9.3
139
4
3.5
139
4
9.3
0177
460
60
111
5
2.8
122
4
2.8
380
60
141
5
3.5
141
5
9.3
154
4
3.5
154
4
9.3
0187
460
60
154
5
2.8
105
5
2.8
380
60
195
5
3.5
195
5
9.3
132
5
3.5
132
5
9.3
0197
460
60
141
5
2.8
141
5
2.8
380
60
179
5
3.5
179
5
9.3
179
5
3.5
179
5
9.3
0207
460
60
141
6
2.8
152
5
2.8
380
60
179
6
3.5
179
6
9.3
193
5
3.5
193
5
9.3
0227
460
60
150
6
2.8
150
6
2.8
380
60
190
6
3.5
190
6
9.3
190
6
3.5
190
6
9.3
0247
460
60
194
6
2.8
149
6
2.8
380
60
245
6
3.5
245
6
9.3
188
6
3.5
188
6
9.3
YCIV
E/V
CONTROL
KVA (7)
UNIT SHORT CIRCUIT WITH-
STAND (KA)
FIELD WIRING & PROTECTION
FIELD WIRING & PROTECTION
STD. & ULTRA QUIET COND. FANS
HIGH HEAD/HIGH STATIC FANS
TWO-SPEED COND. FANS
TERMINAL
BLOCK (STD)
CIRCUIT
BREAKER
(OPT)
MINI-
MUM CKT.
AMPACITY
(MCA) (3)
RECOMMEND-
ED FUSE/CKT.
BREAKER RAT-
ING (4)
MAX. IN-
VERSE TIME
CKT. BRKR.
RATING (2)
MAX DUAL
ELEMENT
FUSE
SIZE (2)
MINIMUM
CKT.
AMPACITY
(MCA) (3)
RECOMMENDED
FUSE/CKT.
BREAKER RAT-
ING (4)
MAX.
INVERSE
TIME CKT.
BRKR. RAT-
ING (2)
MAX DUAL
ELEMENT
FUSE
SIZE (2)
MINIMUM
CKT.
AMPACITY
(MCA) (3)
RECOMMENDED
FUSE/CKT.
BREAKER RAT-
ING (4)
MAX.
INVERSE
TIME CKT.
BRKR.
RATING (2)
MAX DUAL
ELEMENT
FUSE
SIZE (2)
0157
1.8
30KA
65KA
270
300
350
350
1.8
30KA
65KA
341
400
450
450
388
450
500
500
0177
1.8
30KA
65KA
288
350
400
400
1.8
30KA
65KA
365
450
500
500
417
500
500
500
0187
1.8
30KA
65KA
325
400
450
450
1.8
30KA
65KA
411
500
600
600
469
600
600
600
0197
1.8
30KA
65KA
345
400
450
450
1.8
30KA
65KA
437
500
600
600
495
600
600
600
0207
1.8
30KA
65KA
362
450
500
500
1.8
30KA
65KA
458
600
600
600
522
600
700
700
0227
1.8
30KA
65KA
371
450
500
500
1.8
30KA
65KA
469
600
600
600
539
600
700
700
0247
1.8
30KA
65KA
424
500
600
600
1.8
30KA
65KA
536
700
700
700
606
700
800
800
See page 92 for Electrical Data footnotes.
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...