JOHNSON CONTROLS
266
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
SECTION 8 - MICROPANEL
Low Ambient Temp Cutout
OPTIONS LOW AMBIENT TEMP CUTOUT
◄ ► XXXXXXXXXXXXXXXXXXXX
This message indicates whether the low ambient cutout
was enabled or disabled at the time of the fault.
Remote Current Reset
OPTIONS REMOTE CURRENT LIMIT INPUT
◄ ►
DISABLED
OPTIONS REMOTE CURRENT LIMIT INPUT
◄ ► 0.0 TO 10.0 VOLTS DC
OPTIONS REMOTE CURRENT LIMIT INPUT
◄ ► 2.0 TO 10.0 VOLTS DC
OPTIONS REMOTE CURRENT LIMIT INPUT
◄ ► 0.0 TO 20.0 MILLIAMPS
OPTIONS REMOTE CURRENT LIMIT INPUT
◄ ► 4.0 TO 20.0 MILLIAMPS
This message indicates whether remote current reset
was active or disabled at the chiller keypad at the time
of the fault and if active, the type of reset signal select-
ed. One of the following messages will be indicated:
DISABLED (no signal)
•
0 to 10VDC
•
2 to 10VDC
•
0 to 20ma
•
4 to 20ma.
If the option is not factory enabled, the option will not
appear.
Program Values
Suction Pressure Cutout
PROGRAM
SUCTION PRESSURE CUTOUT = XXX.X PSIG
This message indicates the he suction pressure cutout
programmed at the time of the fault.
Low Ambient Cutout
PROGRAM
LOW AMBIENT TEMP CUTOUT = XXX.X °F
This message displays the low ambient temp cutout
programmed at the time of the fault.
Low Leaving Chilled Liquid Temp Cutout
PROGRAM
LEAVING LIQUID TEMP CUTOUT = XXX.X °F
This message displays the low leaving Chilled liquid
temperature cutout programmed at the time of the fault.
Motor Current Limit
PROGRAM
MOTOR CURRENT LIMIT = XXX %FLA
This message indicates the motor current limit pro-
grammed at the time of the fault.
Pulldown Current Limit
PROGRAM
PULLDOWN CURRENT LIMIT = XXX %FLA
This message indicates the pulldown current limit pro-
grammed at the time of the fault.
Pulldown Current Limit Time
PROGRAM
PULLDOWN CURRENT LIMIT TIME = XXX MIN
This message indicates the pulldown current limit time
programmed at the time of the fault.
Suction Superheat Setpoint
PROGRAM
SUCTION SUPERHEAT SETPOINT = XXX.X °F
This message indicates the suction superheat setpoint
programmed at the time of the fault.
Unit ID Number
PROGRAM
REMOTE UNIT ID NUMBER = X
This indicates the unit ID # programmed at the time of
the fault.
Sound Limit Setpoint
PROGRAM
SOUND LIMIT SETPOINT = XXX %
This indicates the sound limit setpoint programmed at
the time of the fault, if the sound limit option is activat-
ed at the factory. If the option is not factory activated,
the display will not appear.
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...