![Johnson Controls YCIV0157 Installation Operation & Maintenance Download Page 84](http://html1.mh-extra.com/html/johnson-controls/yciv0157/yciv0157_installation-operation-and-maintenance_2023452084.webp)
JOHNSON CONTROLS
84
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
SECTION 6 - TECHNICAL DATA
HIGH EFFICIENCY 2-COMPRESSOR UNITS (CONT'D)
HIGH EFFICIENCY YCIV_ _ _ _ E/V
MODEL NO./NAMEPLATE
FIELD WIRING LUGS
STD TERMINAL
BLOCK STD.,
U.Q. & TWO-SPD
COND. FANS
OPT CIRCUIT
BREAKER STD.,
U.Q. & 2-SPD
COND. FANS
STD TERMINAL
BLOCK HIGH
HEAD/HIGH STAT-
IC COND. FANS
OPT CIRCUIT
BREAKER HIGH
HEAD/HIGH STAT-
IC COND. FANS
YCIV E/V
INPUT
VOLTS
(9)
INPUT
FREQ
LUGS/
PHASE
(1)
LUG
WIRE
RANGE
LUGS/
PHASE
(1)
LUG
WIRE
RANGE
LUGS/
PHASE
(1)
LUG
WIRE
RANGE
LUGS/
PHASE
(1)
LUG
WIRE
RANGE
0157
460
60
2
#2 - 600
KCM
2
#2/0 - 500 KCM
380
60
2
#2 - 600
KCM
2
#2/0 - 500 KCM
3
#2 - 600
KCM
3
#3/0 -
400 KCM
0177
460
60
2
#2 - 600
KCM
2
#2/0 - 500 KCM
380
60
2
#2 - 600
KCM
2
#2/0 - 500 KCM
3
#2 - 600
KCM
3
#3/0 -
400 KCM
0187
460
60
2
#2 - 600
KCM
2
#2/0 - 500 KCM
380
60
2
#2 - 600
KCM
2
#2/0 - 500 KCM
3
#2 - 600
KCM
3
#3/0 -
400 KCM
0197
460
60
2
#2 - 600
KCM
2
#2/0 - 500 KCM
380
60
2
#2 - 600
KCM
2
#2/0 - 500 KCM
3
#2 - 600
KCM
3
#3/0 -
400 KCM
0207
460
60
2
#2 - 600
KCM
2
#2/0 - 500 KCM
380
60
2
#2 - 600
KCM
2
#2/0 - 500 KCM
3
#2 - 600
KCM
3
#3/0 -
400 KCM
0227
460
60
2
#2 - 600
KCM
2
#2/0 - 500 KCM
380
60
2
#2 - 600
KCM
2
#2/0 - 500 KCM
3
#2 - 600
KCM
3
#3/0 -
400 KCM
0247
460
60
2
#2 - 600
KCM
2
#2/0 - 500 KCM
380
60
3
#2 - 600
KCM
3
#3/0 - 400 KCM
3
#2 - 600
KCM
3
#3/0 -
400 KCM
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...