SECTION 8 - MICROPANEL
Sensor Displays
lists all the sensors attached
to the control board associated with system data keys.
The minimum and maximum values displayed on the
micro display are provided.
If values exceed the limits in the table, a < (less than)
or > (more than) sign will be display along with the
minimum or maximum value.
TABLE 15 -
SENSOR MIN/MAX OUTPUTS
SENSOR
TYPE
MINIMUM
MAXIMUM
Suction
Pressure
Transducer
0.0 PSIG
125.0 PSIG
Oil
Pressure
Transducer
0.0 PSIG
275.0 PSIG
Discharge
Pressure
Transducer
0.0 PSIG
275.0 PSIG
Flash Tank
Level
Capacitance
0.0%
100 %
Leaving Chilled
Liquid Temp.
3Kohm
Thermistor
-19.1ºF
110.2ºF
Return Chilled
Liquid Temp.
3Kohm
Thermistor
-19.1ºF
110.2ºF
Ambient Air
Temp.
10Kohm
Thermistor
-4.6ºF
137.9ºF
Suction
Temp.
3Kohm
Thermistor
-4.1ºF
132.8ºF
Oil Temp.
50Kohm
Thermistor
40.3ºF
302.6ºF
Discharge
Temp.
50Kohm
Thermistor
40.3ºF
302.6ºF
Compressor
Motor Temp.
10Kohm
Thermistor
-30.0ºF
302.0ºF
Remote Temp.
Reset
4-20mA/2-10VDC
0 %
100 %
0-20mA/0-10VDC
Remote
Current Limit
4-20mA/2-10VDC
0 %
100 %
0-20mA/0-10VDC
Remote
Sound Limit
4-20mA/2-10VDC
0 %
100 %
0-20mA/0-10VDC
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...