Actuator status indication

The actuator microprocessor carries out a diagnostics when a failure has been 
detected. The actuator status is indicated by the LED. When the microprocessor 
detects that the stem has come to an unexpected stop it initiates a retry cycle, this is 
repeated three times and if unsuccessful the actuator status is switched to fault 
mode, the yellow LED blinks. 
If the problem is cleared during the retry cycles, the actuator continues its normal 
function.

* If the sticking cause is removed, the actuator leaves the temporary fault mode 
pushing the calibration button for at least 5 s.
** The LED switches back to green when the temperature is back to the an allowed 
temperature value.

Figure 8:  Auxiliary Switches setting

(a). 

CAM for auxiliary switches.

The auxiliary switches can be adjusted by means of the two cams.

Safety Warnings

• To prevent electric shock or damage to equipment, great care must be taken when 

the cover is removed (by authorised personnel only) for adjustments or inspection. 
In all other cases when the cover is removed, the power should be switched OFF. 
This actuator is not equipped with a power supply switch. Therefore an additional 
bipolar switch should be included in the power supply wiring to isolate the device.

• All wiring should conform to local codes and must be carried out by authorized 

personnel only. Keep high and low voltage wiring separated. 
When using multi-stranded wire apply a cable ferrule to the cable end.

• Make sure that the line power supply is in accordance with the power supply 

specified on the device. Check all wiring connections before applying power to the 
system. Short-circuited wires will result in permanent damage to the equipment. 
24 VAC models must be powered through a class II 230/24V safety transformer and 
appropriate fuse.

• Do not repair or replace a damaged cable, contact the nearest Johnson Controls 

commercial system wholesaler.

• Do not open the actuator other then aux switches or feedback setting.

Check out procedure 

Before leaving the installation observe at least three complete operating cycles to be 
sure that all components are functioning correctly. If not, please contact your supplier.

Ordering Code

Technical Specifications

Table 2: LED indications

LED color

Status

Green

Yellow

Red

On

Power on - 
motor still

• Custom calibration value 

out of range

• Selfcalibration rejected. 

Valve stroke out of limit 
(<8, >25 mm).
Motor still.

Generic fault

Blink

Motor running

• Temporary fault, possible 

valve sticking

*

• Selfcalibration rejected. 

Valve stroke out of limits 
(<8, >25 mm).
Motor running.

High temperature

**

Fast blink

Calibrating

Input signal failure

Off

Power off

Table 3: Feedback output

Input signal

Feedback output

0...10 V or 0...20 mA

0...10 V

2...10 V or 4...20 mA

2...10 V

WARNING: Take care that auxiliary switches S1 and S2 are NOT 
connected to different voltages (E.g. S1 230V and S2 24V NO!, S1 
230V and S2 230V OK!).

Code

Description

VA78x0-GGA-11

Proportional 24 V~, VG7000T valves

VA78x0-GGA-12

Proportional 24 V~, VGS8xxx / VG8000 / VG9000 valves

VA78x0-GGC-11

Proportional 24 V~, 2 auxiliary contacts, VG7000T valves

VA78x0-GGC-12

Proportional 24 V~, 2 auxiliary contacts, VGS8xxx / VG8000 / 

VG9000 valves

Product 

VA7820 - VA7830 Electric Valve Actuators 
Proportional models series

Thrust Force

225 lb (1000 N)

Power Supply

24 V~ (19…30 V~) 50/60 Hz

Power Consumption

11 VA 

Ambient Operating

Conditions

-5...55 °C

10...90% RH (non condensing)

Ambient Storage

Conditions

-40...80 °C

5...95% RH (non condensing)

Feedback signal

0...10 V, with input signal 0...10 V or 0...20 mA 
2...10 V, with input signal 2...10 V or 4...20 mA

Dimensions 

(H x W x D)

231 x 115 x 212 mm 

Housing Material

Self-extinguishing  to UL94-V0

Protection Class

IP54 (IEC 60529)

Shipping Weight

3,3 Kg 

Compliance 

CE Mark, EMC Directive 89/336/EEC, 
Low Voltage Directive 73/23/EEC 

Summary of Contents for VA7820-GG-1 Series

Page 1: ...ls Inc Johnson Controls Inc Building Efficiency Headquarters Milwaukee Wisconsin USA Branch Offices Principal Cities World wide www johnsoncontrols com VA7820 GGx 1x VA7830 GGx 1x Electric Valve Actua...

Page 2: ...820 VA7830_P N 14 88375 25 Rev A_06 2009 This document is subject to change without notice Figure 4 Mounting Actuator on the valve mod VA78x0 xxx 11 Figure 5 Mounting Actuator on the valve mod VA78x0...

Page 3: ...VA7820 VA7830_P N 14 88375 25 Rev A_06 2009 This document is subject to change without notice Figure 7 Starting Self Calibration Figure 6 Wiring diagram VA78x0 GGx xx Figure 8 Auxiliary Switches setti...

Page 4: ...will make one full cycle to detect the stem extended and retracted limits The end stroke cursors are automatically placed at the stroke limits Standard input signal DIP SWITCH 3 OFF The green LED swit...

Page 5: ...owered through a class II 230 24V safety transformer and appropriate fuse Do not repair or replace a damaged cable contact the nearest Johnson Controls commercial system wholesaler Do not open the act...

Page 6: ...demi coupleurs 7 D placer manuellement les indices de fin de course contre l indicateur C blage Figure 6 Sch ma de c blage VA78x0 GGx 1x a C blage en proportionnelle b C blage en flottante c C blage e...

Page 7: ...it tre conforme aux codes locaux et effectu uniquement par du personnel habilit S parer les c bles haute et basse tension En cas d utilisation d un c ble multibrin poser une bague son extr mit V rifie...

Page 8: ...sitionsmarken von Hand gegen die Anzeige schieben Anschluss Abbildung 6 Beschaltungsplan f r VA78x0 GGx 1x a Beschaltung f r Proportionalregelung b Beschaltung f r 3 Punkt Regelung c Beschaltung f r 2...

Page 9: ...htung muss den rtlichen Bestimmungen entsprechen und darf nur von qualifiziertem Fachpersonal vorgenommen werden Nieder und Hochspannungskabel m ssen voneinander getrennt gehalten werden Bei der Verwe...

Page 10: ...Montaggio corretto dei mezzi giunti 7 Spostare manualmente i cursori di fine corsa contro l indicatore Cablaggio Figura 6 Schema di cablaggio VA78x0 GGx 1x a Cablato come proporzionale b Cablato come...

Page 11: ...ne di isolare il dispositivo Tutti i cablaggi devono essere conformi ai codici locali e devono essere eseguiti solo da personale autorizzato Tenere separati i cablaggi ad alta e bassa tensione Quando...

Page 12: ...e correcto de los semiacopladores 7 Mueva manualmente los cursores de fin de carrera hacia el indicador Cableado Figura 6 Diagrama de cableado de VA78x0 GGx 1x a Cableado proporcional b Cableado flota...

Page 13: ...slar el dispositivo Todo el cableado debe cumplir la normativa local y su instalaci n se confiar exclusivamente al personal autorizado Mantenga separados los cables de alta y baja tensi n Si se utiliz...

Page 14: ...montage van halfkoppelingen 7 Beweeg de slag eindecursoren handmatig tegen de indicator in Bedrading Figuur 6 Bedradingsschema voor VA78x0 Gx 1x a Bedraad als Proportioneel b Bedraad als Variabel c Be...

Page 15: ...ust met een stroomschakelaar Hierdoor moet een extra bipolaire schakelaar op de voedingskabels worden aangesloten om het apparaat te isoleren Alle bedrading moet voldoen aan plaatselijke voorschriften...

Page 16: ...ebrytarna placeras automatiskt vid ndl gena Standarding ngssignal VIPPBRYTARE 3 OFF Den gr na lysdioden lyser med fast sken n r nskat l ge har n tts Om styrsignalens v rde ndras flyttas st lldonets st...

Page 17: ...on Controls terf rs ljare St lldonet f r endast ppnas i samband med inst llning av hj lpkontakter eller terf ring Avslutande kontroll F r att s kerst lla att monteringen och inst llningen av st lldone...

Page 18: ...hem operace zelen indik tor LED rychle blik Spou t provede jeden pln cyklus aby byly zji t ny hranice nejvy a nejni polohy h dele Kurzory konce cyklu budou um st ny automaticky v z vislosti na hranic...

Page 19: ...oc bezpe nostn ho m ni e 230 24 V t dy II s vhodnou pojistkou Po kozenou kabel neopravujte ani nevym ujte M sto toho se obra te na nejbli velkoobchod komer n ch syst m Johnson Controls Spou t neotv re...

Page 20: ...Przesun r cznie przesuwki skoku do wska nika Okablowanie Rysunek 6 Schemat okablowania modelu VA78x0 GGx 1x a Okablowanie proporcjonalne b Okablowanie astatyczne c Okablowanie ON OFF d Tylko w przypad...

Page 21: ...biegunowy Okablowanie musi by zgodne z lokalnymi przepisami i mo e by przeprowadzane wy cznie przez uprawniony personel Nale y odizolowa kable niskiego napi cia od okablowania wysokiego napi cia W prz...

Reviews: