58
UMG 96RM-E
RS485 device address (Addr. 000)
If multiple devices are connected to each other via
the RS485 interface, a master device can only identify
the devices by their device address. Within a network,
each device must have its own device address.
Addresses can be set in the range of 1 to 247.
C
The adjustable range of the device address
is between 0 and 255. Values 0 and 248
through 255 are reserved and may not
be used.
Setting
Baud rate
0
9.6kbps
1
19.2kbps
2
38.4kbps
3
57.6kbps
4
115.2kbps (factory setting)
RS485 baud rate (Addr. 001)
A common baud rate can be adjusted for the RS485
interfaces. The baud rate must be uniform for all
devices on the network. Address 003 can be used to set
the number of stop bits (0=1bit, 1= 2bits). Data bits (8)
are fixed default values.