110
UMG 96RM-E
Table 2 - Modbus address list
(frequently needed measured values)
19000
808
float
RD
V
Voltage L1-N
19002
810
float
RD
V
Voltage L2-N
19004
812
float
RD
V
Voltage L3-N
19006
814
float
RD
V
Voltage L1-L2
19008
816
float
RD
V
Voltage L2-L3
19010
818
float
RD
V
Voltage L3-L1
19012
860
float
RD
A
Current, L1
19014
862
float
RD
A
Current, L2
19016
864
float
RD
A
Current, L3
19018
866
float
RD
A
Vector sum; IN=I1+I2+I3
19020
868
float
RD
W
Real power L1
19022
870
float
RD
W
Real power L2
19024
872
float
RD
W
Real power L3
19026
874
float
RD
W
Sum; Psum3=P1+P2+P3
19028
884
float
RD
VA
Apparent power S L1
19030
886
float
RD
VA
Apparent power S L2
Modbus
address
Address
via Display
Format
RD/WR
Unit
Note
C
The addresses contained in the description
can be adjusted directly on the device in
the range from 0 to 800.
The address range 800-999 is available for
programming comparators on the device.
The addresses above 1000 can only be
processed via modbus!
C
A complete overview of the parameters and
measured values as well as explanations
regarding the selected measured values
is filed in the document “Modbus Address
List” on the CD or Internet.