104
UMG 96RM-E
Function parameters
Function
Symbol
Precision class
Measurement range
Display range
Total effective power
P
0.5
5)
(IEC61557-12)
0 .. 5.4 kW
0 W .. 999 GW *
Total reactive power
QA, Qv
1 (IEC61557-12)
0 .. 5.4 kvar
0 varh .. 999 Gvar *
Total apparent power
SA, Sv
0.5
5)
(IEC61557-12)
0 .. 5.4 kVA
0 VA .. 999 GVA *
Total active energy
Ea
0.5S
5) 6)
(IEC61557-12)
0 .. 5.4 kWh
0 Wh .. 999 GWh *
Total reactive power
ErA, ErV
1 (IEC61557-12)
0 .. 5.4 kvarh
0 varh .. 999 Gvarh *
Total apparent energy
EapA, EapV
0.5
5)
(IEC61557-12)
0 .. 5.4 kVAh
0 VAh .. 999 GVAh *
Frequency
f
0.05 (IEC61557-12)
45 .. 65Hz
45.00Hz .. 65.00Hz
Phase current I1 - I3
I
0.2 (IEC61557-12)
0 .. 6 Arms
0 A .. 999 kA
Measured neutral conductor current l4 IN
1 (IEC61557-12)
0 .. 6 Arms
0 A .. 999 kA
Residual currents I5, I6
I
Res
1 (IEC61557-12)
0 .. 40 mArms
0 A .. 999 kA
Computed neutral conductor current
INc
1.0 (IEC61557-12)
0.03 .. 25 A
0.03 A .. 999 kA
Voltage
U L-N
0.2 (IEC61557-12)
10 .. 300 Vrms
0 V .. 999 kV
Voltage
U L-L
0.2 (IEC61557-12)
18 .. 520 Vrms
0 V .. 999 kV
Power factor
PFA, PFV
0.5 (IEC61557-12)
0.00 .. 1.00
0.00 .. 1.00
Short-term flicker, long-term flicker
Pst, Plt
-
-
-
Voltage drops (L-N)
Udip
-
-
-
Voltage increases (L-N)
Uswl
-
-
-
Transient overvoltages
Utr
-
-
-
Voltage drops
Unit
-
-
-
Voltage unbalance (L-N)
1)
Unba
-
-
-
Voltage unbalance (L-N)
2)
Unb
-
-
-
Voltage harmonics
Uh
Kl. 1 (IEC61000-4-7)
up to 2.5 kHz
0 V .. 999 kV
THD of the voltage
3)
THDu
1.0 (IEC61557-12)
up to 2.5 kHz
0 % .. 999 %
THD of the voltage
4)
THD-Ru
-
-
-
Summary of Contents for UMG 96 RM-E