101
UMG 96RM-E
Current measurement I1 - I4
Rated current
5A
Measurement range
0 .. 6A
rms
Crest factor
1.98
Resolution
0.1mA (Display 0.01A)
Overvoltage category
300V CAT II
Measurement surge voltage
2kV
Power consumption
approx. 0.2 VA (Ri=5mOhm)
Overload for 1 sec.
120A (sinusoidal)
Sampling frequency
20kHz
Residual current measurement I5 / I6
Rated current
30mA
rms
Measurement range
0 .. 40mA
rms
Operating current
50
µ
A
Resolution
1
µ
A
Crest factor
1.414 (related to 40mA)
Burden
4 Ohm
Overload for 1 sec.
5A
Sustained overload
1A
Overload for 20 ms
50A
Residual current measurement
i.a.w. IEC/TR 60755 (2008-01), Type A
Type B