Averaging method
The applied exponential messaging method reaches at
least 95% of the measurement value once the reporting
time has run its course.
Min. and max. values
All measured values are measured and calculated during
all 10/12 periods. Minimum and maximum values are
determined for most measured values.
The min. value is the smallest measured value determined
since the last deletion. The max. value is the highest
measured value determined since the last deletion.
All minimum and maximum values are compared with
the corresponding measured values and overwritten
when exceeded or fallen short of.
The minimum and maximum values are saved every
5 minutes in an EEPROM without date and time. Thus,
the minimum and maximum values of the past 5 minutes
may be lost due to an operating voltage failure.
Delete min. and max. values (Addr.506)
If „001“ is set for address 506, all minimum and maximum
values can be deleted simultaneously.
Parameter
Mean value
Mean values are averaged over an adjustable period
for the current, voltage and power measured values.
The mean values
are indicated by a bar over the
measured value.
The averaging time can be selected from a list with 9
fixed averaging times.
Averaging time, current (Addr. 040)
Averaging time, power (Addr. 041)
Averaging time, voltage (Addr. 042)
Setting
Averaging time/sec.
0
5
1
10
2
15
3
30
4
60
5
300
6
480 (factory setting)
7
600
8
900