52
UMG 806
www.janitza.com
10.3 Parameter list
·Parameter addresses are
not
Modbus addresses!
·Modbus addresses can be found in the separate
Modbus address list in the download area at
www.janitza.com
Address
Format
Designation
Setting range
Unit
Default
setting
000
uint32
Current transformer primary, I1..I3
1 .. 9999999
5
001
uint16
Current transformer secondary, I1..I3 1 .. 6
5
002
uint32
Voltage transformer primär, L1..L3
1 .. 9999999
380
003
uint16
Voltage transformer secondary, L1..
L3
1 .. 690
380
010
uint32
Current transformer primary, I4
1 .. 9999
5
011
uint16
Current transformer secondary, I4
1 .. 6
5
020
uint32
Current transformer primary, I5
1 .. 9999
5
021
uint16
Current transformer secondary, I5
1 .. 9999
5
110
uint16
Network system/wiring
0 : 3P4W
1 : 3P3W
2 : 1P2W
0, 1, 2
0
113
uint16
Deletes all energy data (1 : delete)
0.1
114
uint16
Resets all recordings (1 = reset)
0.1
115
uint16
Resets all min. and max. values
(1 = reset)
0.1
Address Format
Designation
Setting range
Unit
Default
setting
200
uint8
Device address
1 .. 247
1
201
uint8
Baud rate, RS-485
0 = 9,600 bit/s
1 = 19,200 bit/s
2 = 38,400 bit/s
3 = 57,600 bit/s
4 = 115,200 bit/s
0 .. 7
3
202
uint8
RS-485, parity
0 = N.8.1
1 = E.8.1
2 = O.8.1
3 = N.8.2
0 .. 3
0
203
uint8
RS-485, mode
0 = Modbus RTU/Slave
1 = Master
0.1
0