10. Confi guration
10.1 Confi guration mode
The confi guration mode is used to confi gure the
parameters necessary for the operation of the
device. The device requires the supply voltage for
confi guration.
· Press and hold buttons 1 and 2 simultaneously
for 1 s to switch between the display and confi g-
uration modes.
· A password request (standard setting 0000 - no
password - see the section Password) takes you
to the confi guration mode.
· In confi guration mode, the character appears
on the display.
WARNING
Risk of injury due to electrical voltage!
Severe bodily injury or death can result from:
· Touching bare or stripped leads that are ener-
gized.
· Terminals / inputs of the device that pose a
hazard when touched.
Therefore please abide by the following
· Cover or block off adjacent live parts!
· Use non-conductive tools and wear protective
clothing.
· Inform yourself about applicable safety guide-
lines.
10.2 Confi guration
· Press and hold buttons 1 and 2 simultaneously
for 1 s to switch between the display and confi g-
uration modes.
· Enter the code (password) in the display
by pressing button 1 (confi rm or change digit
position) and button 2 (increment digit).
- Default setting
0000 - no password
· The 1st parameter address 000 for confi guration
of the primary current transformers I1 ..I3 ap-
pears.
· To complete your confi gurations and save them,
press and hold buttons 1 and 2 simultaneously
for 1 s.
· The device then switches to the display mode.
Select the parameter to be confi gured according
to the parameter list.
INFORMATION
A parameter list can be found in chapter
„10.3 Pa-
rameter list“ on page 52.
Function of the buttons in the confi guration
mode
Button
Function in the confi guration mode
With button 1
· Change the digit position.
· Confi rm your input/number.
With button 2
· Increment the activated digit or
change the decimal place.
· To save your changes and switch to
the display mode, press buttons 1
and 2 simultaneously for 1 s!
Tab.: Function buttons
10.2.1 Confi guring the network system
Confi gure your network system in the following
parameter address:
Address
Designation
110
Network system/wiring
0 : 3P4W (default setting)
1 : 3P3W
2 : 1P2W
Confi gure the parameters above as already de-
scribed in section „10.2 Confi guration“ on page
47.