67
UMG 806
www.janitza.com
- The selection "DI3_1" indicates, for example,
that the third digital input is active.
- 1 describes that the output relay is set when
the corresponding switching state is present
at the input.
- If "DI3_0" is selected as the input specifica-
tion, the relay output is only set if there is no
input signal and if the input circuit is open.
INFORMATION
A detailed parameter list can be found in chapter
„10.3 Parameter list“ on page 52.
13.8.2 Manual control via Modbus addresses
For control of the relays, configure a "2" in param-
eter address 410 (default setting) as described
in chapter „10.2 Configuration“ on page 47. In
addition, the pulse width (parameter address 411)
must be set to "s".
Pulse width:
The resolution is 0.01 s with a setting range of 0.1
- 99.99 s.
Modbus address set to 1 = ON
Modbus address set to 0 = OFF
Modbus address 30160
EI1-RO1
Modbus address 30161
EI1-RO2
Modbus address 30162
ED1-RO1
Modbus address 30163
ED1-RO2
If the pulse width is set to 0 s, the relay is in level
mode: the relay remains in the preset status (active
or inactive, the time period set is not relevant in
level mode) until a control signal via the Modbus
addresses changes this status.
(See also Modbus address list, UMG 806 at
www.janitza.com)
You can configure the relay outputs in the following
parameter addresses:
Address
Designation
410
EI1-RO1 mode
0=Off, 1=Alarm, 2=Remote control
(default setting)
411
EI1-RO1 pulse width
0 .. 99.99
412
EI1-RO1 alarm element
(Reference Communication Address
- see Modbus address 30030) 0..61
(see „13.8.3 Table “Parameters of the
alarm elements” - addresses (412,
413
EI1-RO1 alarm value
0 - 9999
414
EI1-RO1 hysteresis value
0 - 9999 (default = 0)
415
EI1-RO1 delay time
0 - 9999
420-425
EI1-RO2
430-435
ED1-RO1(DO3)
440-445
ED1-RO2(DO4)
Summary of Contents for UMG 806