87
UMG 806
www.janitza.com
Voltage measurement
3-phase 4-conductor systems with rated voltages up to
230 VLN / 400 VLL (+/-10%) acc. to IEC
3-phase 3-conductor systems (grounded) with rated voltages up to
400 VLL (+/-10%) acc. to IEC
Overvoltage category
300 V CAT III according to IEC
Rated surge voltage
4 kV
Protection of the voltage measurement
1 - 10 A tripping characteristic B (with IEC/UL approval)
Measuring range L-N
0
.. 230 Veff (max. overvoltage 277 Veff)
Measuring range L-L
0
.. 400 Veff (max. overvoltage 480 Veff)
Resolution
0.1 V
Crest factor
2 (referred to measuring range 230 V L-N)
Impedance
>1.7 MΩ/Phase
Power consumption
approx. 0.1 VA / phase
Sampling frequency
8 kHz / phase
Frequency of fundamental oscillation
- Resolution
45 Hz .. 65 Hz
0.01 Hz
Harmonics
1 .. 31.
Current measurement (../1 A) (../5 A)
Nominal current
5 A
Channels
4
Measuring range
0.005 .. 6 Aeff
Crest factor (relative to the nominal current)
2
Overload for 1 s
100 A (sinusoidal)
Resolution
1 mA
Overvoltage category
300 V CATII
Rated surge voltage
4 kV
Power consumption
approx. 0.2 VA
Sampling frequency
8 kHz
Harmonics
1 .. 31.
Current measurement (measuring range 0 .. 40 mA, AC)
Channel I5
1
Summary of Contents for UMG 806
Page 9: ...9 UMG 806 www janitza com...
Page 21: ...21 UMG 806 www janitza com...
Page 55: ...55 UMG 806 www janitza com...
Page 62: ...62 UMG 806 www janitza com 13 3 Front side views 13 3 1 806 EC1 module 13 3 2 806 ED1 module...
Page 81: ...81 UMG 806 www janitza com...
Page 85: ...85 UMG 806 www janitza com...