10.2.7 Configuring the RS-485 interface (Mod-
bus)
To operate the device via the RS-485 interface (see
chapter „7.8 RS-485 interface“ on page 38),
configure the following parameter addresses:
·Device address
·Baud rate
·Parity
·Operating mode
Address
Designation
200
Device address (1 .. 247)
201
Baud rate, RS-485
0 = 9,600 bit/s
1 = 19,200 bit/s
2 = 38,400 bit/s
3 = 57,600 bit/s
4 = 115,200 bit/s
202
RS-485, parity
0 = N.8.1
1 = E.8.1
2 = O.8.1
3 = N.8.2
203
RS-485, mode
0 = Modbus RTU/slave
1 = Modbus RTU/master
Tab.: Configuration of the RS-485 interface
Configure the parameters above as already de-
scribed in section „10.2 Configuration“ on page
47.
INFORMATION
A parameter list can be found in chapter „10.3