19
UMG 806
www.janitza.com
3.8
Transformer
Please note! It is not permitted to use the outputs
of Janitza measurement devices and components
for switching protective devices or protective re-
lays! Use
only
“Current transformers for measuring
purposes” for Janitza measurement devices and
Janitza components!
“Transformers”, unlike “protection transformers”,
go into saturation at high current peaks. “Pro-
tection transformers” do not have this saturation
behavior and can therefore significantly exceed
the rated values in the secondary circuit. This can
overload the current measurement inputs of the
measurement devices!
Furthermore, please note that Janitza measure-
ment devices and components are
not
to be used
for critical switching, control or protection applica-
tions (protective relays)!
Observe the safety and warning information in the
chapters „7. Installation“ on page 28 and „2.3
Product safety“ on page 13!
3.9
Operating concept
The following options are offered for operating,
configuring or reading the meter:
·
2 function buttons with display
for configura-
tion and acquisition of data.
A standard Modbus address list is available at
www.janitza.com.
This user manual describes how to operate the
meter using 2 buttons. The GridVis
®
software has
"online help" and e-learning instructions.
3.10 GridVis
®
network analysis software
Use the GridVis
®
network analysis software avail-
able at www.janitza.com to read out data for anal-
ysis. To do so, connect a PC to your measurement
device via the Ethernet interface.
Performance characteristics of the GridVis
®
software
·Read out the device.
·Graphic display of measured values.
·Analysis of read data.
·Create reports.
Connections to the PC
Connections for communication between the PC
and the measurement device can be found in
chap. „8.1 Connection to a PC“ on page 42.