103
UMG 509-PRO
www.janitza.com
15.4 Temperature measurement input
Temperature measurement input
3-wire measurement
Update time
1 second
Connectable sensors
PT100, PT1000, KTY83, KTY84
Total load (sensor and cable)
max. 4 kOhms
Cable length
up to 30 m not shielded; greater than 30 m shielded
Sensor type
Temperature range
Resistance range
Measurement uncer-
tainty
KTY83
-55 °C ... +175 °C
500 ohms ... 2.6 kOhms
±1.5% rng
KTY84
-40 °C ... +300 °C
350 ohms ... 2.6 kOhms
±1.5% rng
PT100
-99 °C ... +500 °C
60 ohms ... 180 ohms
±1.5% rng
PT1000
-99 °C ... +500 °C
600 ohms ... 1.8 kOhms
±1.5% rng
Connection capacity of the terminal points (temperature measurement input)
Connectible conductors. Only one conductor may be connected per terminal point!
Single core, multi-core, fine-stranded
0.08 - 1.5 mm
2
Terminal pins, wire end ferrules
1 mm
2
Potential isolation and electrical safety of the temperature measurement inputs
·The temperature measurement input is double insulated relative to the current and voltage measure-
ment inputs as well as to the supply voltage.
·There is no insulation to the RCM measurement input.
·There is only a functional insulation relative to the Ethernet, Profibus, RS-485 and digital I/O interfac-
es.
·The external temperature sensor must be double insulated relative to hazardous contact voltage (ac-
cording to IEC61010-1:2010).