UMG 509-PRO
84
www.janitza.com
12.12 Recording configuration
Two recording profiles are preconfigured
in the factory default setting of the device.
Adaptation and expansion of recordings can be
done using the GridVis® software.
Profile Measured value
Time base
Type
1
RMS voltage
L1, L2, L3, L4, L1-L2, L2-L3, L3-L1
15 min.
average value (arithmetic),
Min./max. values
1
RMS current L1, L2, L3, L4
15 min.
average value (arithmetic),
Min./max. values
1
Active power L1, L2, L3, L4
15 min.
average value (arithmetic),
Min./max. values
1
Active power, sum L1..L3, L1..L4
15 min.
average value (arithmetic),
Min./max. values
1
Reactive power, fundamental
L1, L2, L3, L4
15 min.
average value (arithmetic),
Min./max. values
1
Reactive power, fundamental, sum L1..L3, L1..
L4
15 min.
average value (arithmetic),
Min./max. values
2
Consumed active energy L1, L2, L3, L4
1 hr.
Sample
2
Consumed active energy, sum
L1..L3, L1..L4
1 hr.
Sample
2
Inductive reactive energy L1, L2, L3, L4
1 hr.
Sample
2
Inductive reactive energy sum
L1..L3, L1..L4
1 hr.
Sample