105
UMG 509-PRO
www.janitza.com
15.6 Interfaces
RS-485 interface
3-wire connection with GND, A, B
Protocol
Modbus RTU/Slave, Modbus RTU/Master,
Modbus RTU /Gateway
Transmission rate
9.6 kbps, 19.2 kbps, 38.4 kbps, 57.6 kbps, 115.2
kbps, 921.6 kbps
Termination resistor
can be activated via microswitch
Profibus interface
Connection
SUB D 9-pin
Protocol
Profibus DP/V0 according to EN 50170
Transmission rate
9.6 kBaud to 12 MBaud
Ethernet interface
Connection
RJ45
Function
Modbus gateway, embedded web server (HTTP)
Protocols
CP/IP, EMAIL (SMTP), DHCP client (BootP),
Modbus/TCP, Modbus RTU over Ethernet, FTP, ICMP
(Ping), NTP, TFTP, BACnet (option), SNMP
Potential isolation and electrical safety of the interfaces
·The RS-485, Profibus and Ethernet interfaces are double insulated relative to the current and voltage
measurement inputs and the supply voltage.
·There is only a functional insulation from each other and from the RCM and temperature measure-
ment inputs as well as from the digital I/Os.
·The interfaces of the devices connected here must have double or reinforced insulation against mains
voltages (according to IEC 61010-1: 2010).