UMG 509-PRO
106
www.janitza.com
15.7 Performance characteristics of functions
The measurements are made via current transformers ../5 A with a frequency of 50 / 60 Hz.
INFORMATION
Note on saving measured values and configuration data:
Since the following measured values are stored in a non-volatile memory every 5 minutes, an
operating
voltage failure
can result in an interruption of the recording of max. 5 minutes:
·
Comparator timer
·
S0 meter readings
·
Min. / max. / average values
(without date and time)
·
Energy values
Configuration data is saved immediately.
A detailed Modbus address and parameter list can be found at www.janitza.com.
Function
Symbol
Accuracy class
Measuring range
Display range
Total active power
P
0.2
5)
(IEC61557-12)
0 .. 15.3 kW
0 W .. 9999 GW *
Total reactive power
QA
6)
, Qv
6)
1 (IEC61557-12)
0 .. 15.3 kvar
0 varh .. 9999 Gvar *
Total apparent power
SA, Sv
6)
0.2
5)
(IEC61557-12)
0 .. 15.3 kVA
0 VA .. 9999 GVA *
Total active energy
Ea
0.2
5)
(IEC61557-12)
0.2S
5)
(IEC62053-22)
0 .. 15.3 kWh
0 Wh .. 9999 GWh *
Total reactive energy
ErA
6)
, ErV
6)
1 (IEC61557-12)
0 .. 15.3 kvarh
0 varh .. 9999 Gvarh *
Total apparent energy
EapA,EapV
6)
0.2
5)
(IEC61557-12)
0 .. 15.3 kVAh
0 VAh .. 9999 GVAh *
Frequency
f
0.05 (IEC61557-12)
40 .. 70 Hz
40 Hz .. 70 Hz
Phase current
I
0.2 (IEC61557-12)
0.005 .. 7 Arms
0 A .. 9999 kA
Neutral conductor current measured
IN
0.2 (IEC61557-12)
0.005 .. 7 Arms
0 A .. 9999 kA
Residual currents I5, I6
IDIFF
1 (IEC61557-12)
0 .. 40 mArms
0 A .. 9999 kA
Neutral conductor current calculated
INc
0.5 (IEC61557-12)
0.005 .. 21 A
0 A .. 9999 kA
Voltage
U L-N
0.1 (IEC61557-12)
10 .. 600 Vrms
0 V .. 9999 kV
Voltage
U L-L
0.1 (IEC61557-12)
18 .. 1000 Vrms
0 V .. 9999 kV
Power factor
PFA, PFV
0.5 (IEC61557-12)
0.00 .. 1.00
0 .. 1
Short-term flicker, long-term flicker
Pst, Plt
-
-
-
Voltage dips
Udip
0.2 (IEC61557-12)
10 .. 600 Vrms
0 V .. 9999 kV
Voltage swells
Uswl
0.2 (IEC61557-12)
10 .. 600 Vrms
0 V .. 9999 kV
Transient overvoltages
Utr
0.2 (IEC61557-12)
10 .. 600 Vrms
0 V .. 9999 kV
Voltage interruptions
Uint
-
-
-
Voltage unbalance
1)
Unba
0.2 (IEC61557-12)
10 .. 600 Vrms
0 V .. 9999 kV
Voltage unbalance
2)
Unb
0.2 (IEC61557-12)
10 .. 600 Vrms
0 V .. 9999 kV
Voltage harmonics
Uh
Cl. 1 (IEC61000-4-7)
Up to 2.5 kHz
0 V .. 9999 kV
THD of voltage
3)
THDu
1.0 (IEC61557-12)
Up to 2.5 kHz
0% .. 999%
THD of voltage
4)
THD-Ru
1.0 (IEC61557-12)
Up to 2.5 kHz
0% .. 999%
Current harmonics
Ih
Cl. 1 (IEC61000-4-7)
Up to 2.5 kHz
0 A .. 9999 kA
THD of current
3)
THDi
1.0 (IEC61557-12)
Up to 2.5 kHz
0% .. 999%
THD of current
4)
THD-Ri
1.0 (IEC61557-12)
Up to 2.5 kHz
0% .. 999%
Mains signal voltage (interharmonic
voltage)
MSV
-
-
-
1) Referenced to amplitude.
2) Referenced to phase and to amplitude.
3) Referenced to the fundamental oscillation.
4) Referenced to the RMS value.
5) Accuracy class 0.2/0.2S with ../5 A transformer.
Accuracy class 0.5/0.5S with ../1A transformer.
6) Calculation from the fundamental oscillation.
* When the max. total work values are reached,
the display jumps back to 0 W.