-59-
Two terminals for acceleration/deceleration time selection have four state combinations, as listed in
the following table.
Terminal
2
Terminal
1
Acceleration/
deceleration time
selection
Corresponding
parameter
OFF
OFF
Acceleration/Deceleration
time 1
P0.17, P0.18
OFF
ON
Acceleration/Deceleration
time 2
P8.03, P8.04
ON
OFF
Acceleration/Deceleration
time 3
P8.05, P8.06
ON
ON
Acceleration/Deceleration
time 4
P8.07, P8.08
P4.10
DI filter time
0.000s~1.000s
0.010s
☆
It is used to set the software filter time of DI terminal status. If DI terminals are liable to interference
and may cause malfunction, increase the value of this parameter to enhance the anti-interference
capability. However, increase of DI filter time will reduce the response of DI terminals.
P4.11
Terminal command mode
One’s
place
Terminal command mode
00
★
Two-line mode 1
0
Two-line mode 2
1
Three-line mode 1
2
Three-line mode 2
3
Two-line mode 1
4
Three-line mode 2
5
Ten’s
place
Terminal input priority
JOG overrides FWD, REV
0
FWD, REV override JOG
1
One’s place:
This parameter sets the mode in which the Inverter is controlled by external terminals.
0:Two-line mode 1;
DI
x
(
FOR)
DI
y
(
REV)
COM
K1
K2
Summary of Contents for DLB1-0D40S2G
Page 11: ...11 Graph 1 722 30KW product outline dimensions Graph 1 837 55KW product outline dimensions...
Page 12: ...12 Graph 1 875 110KW product outline dimensions Graph 1 9 132 160KW product outline dimensions...
Page 14: ...14 2 Wirings 2 1 Standard wiring diagrams Graph 2 8 0 4 18 5KW inverter wiring diagram...
Page 15: ...15 Graph 2 922 400KW inverter wiring diagram...
Page 159: ...159...