The DLB1 provides totally four groups of acceleration/deceleration time for selection. You can
perform switchover by using a DI terminal.
•
Group 1:
P0.17, P0.18
•
Group 2:
P8.03, P8.04
•
Group 3:
P8.05, P8.06
•
Group 4:
P8.07, P8.08
P0.19
Acceleration/decelera
tion time unit
1s
0
1
★
0.1s
1
0.01s
2
To satisfy requirements of different applications, the DLB1 provides three acceleration/ deceleration
time units, 1s, 0.1s and 0.01s.
Modifying this parameter will make the displayed decimal places change and corresponding
acceleration/deceleration time also change.
P0.21
Frequency offset of
auxiliary frequency
source for X and Y
operation
0.00Hz~ maximum frequencyP0.10
0.00Hz
☆
This parameter is valid only when the frequency source is set to "X and Y operation".
The final frequency is obtained by adding the frequency offset set in this parameter to the X and Y
operation result.
P0.22
Frequency reference
resolution
0.1Hz
1
2
★
0.01Hz
2
It is used to set the resolution of all frequency-related parameters.
If the resolution is 0.1 Hz, the DLB1 can output up to 3200 Hz. If the resolution is 0.01 Hz, the DLB1
can output up to 600.00 Hz.
•
Modifying this parameter will make the decimal places of all frequency-related
parameters change and corresponding frequency values change.
•
This parameter is not resumed when factory setting is resumed.
P0.23
Retentive of digital
setting frequency
upon power failure
Not retentive
0
0
☆
Retentive
1
This parameter is valid only when the frequency source is digital setting.
If P0.23 is set to 0, the digital setting frequency value resumes to the value of P0.08 (Preset
frequency) after the Inverter stops. The modification by using keys and or the terminal UP/DOW N
function is cleared.
If P0.23 is set to 1, the digital setting frequency value is the set frequency at the moment when the
Inverter stops. The modification by using keys and or the terminal UP/ DOW N function remains effective.
Summary of Contents for DLB1-0D40S2G
Page 11: ...11 Graph 1 722 30KW product outline dimensions Graph 1 837 55KW product outline dimensions...
Page 12: ...12 Graph 1 875 110KW product outline dimensions Graph 1 9 132 160KW product outline dimensions...
Page 14: ...14 2 Wirings 2 1 Standard wiring diagrams Graph 2 8 0 4 18 5KW inverter wiring diagram...
Page 15: ...15 Graph 2 922 400KW inverter wiring diagram...
Page 159: ...159...