29
In
stal
lat
ion
Wiring
NOTE
• Do not lay on these signal cables in parallel with a power cable. Otherwise the electromagnetic induction
noise is generated and malfunction or failure may result.
• The following products are the recommended SSRs (Solid State Relays) for signal input. Any other SSRs
might cause malfunction. See manufacturer's information for details on these SSRs.
–OMRON G3FD-102S or G3FD-102SN
–OMRON G3TA-IDZR02S or G3TA-IDZR02SM
• When using a mechanical relay for signal input, its minimum application load should be 5mA or below.
• Insert the DIN 4- or 5-pin female connector as far as it will go and then tighten the skirt to make a secure con-
nection.
*Use either a no-voltage contact or an open collector for the input, STOP, and AUX signals.
*Set pulse duration to 10-100ms and the number of pulses at or below 360 pulses per minute.
Detach the terminal case.
Remove four screws and take out the terminal case.
*
The gasket is provided to keep water-/dust-tightness between
the parts. Be sure to replace once it has removed.
Remove the power line and signal line terminal
blocks from the PCB in the control unit.
Remove a cable gland and a cap to pull out a cable gasket.
*
The cap is not used as long as a cable is connected.
Pass an external signal cable into the terminal
case via the cable gland and the cable gasket.
*
Be careful not to oppositely orient the cable gasket.
Cap
Cable gland
Cable gasket
Taper
Cable gland
Cable gasket
Signal-line
terminal block
Power-line
terminal block
2
1
3
4
Control unit
Case gasket
Terminal case
Tapping screw