Goodrive350-19 series VFD Function parameter list
- 379 -
Function
code
Name
Description
Default
value
Modify
protection
frequency
Load
height h
Time t
t1
t2
t3
1st action 2nd action
P93.05
P93.04
P93.05
P93.04
Mechanical
brake failure
Initial
height
Horizon
VFD brake
failure output
Zero servo is used in closed-loop vector control to
check whether the pulse count at stop is greater
than the threshold P93.05. If the threshold is
exceeded, a brake failure alarm is reported. The
output can be set through relay. After the time
P93.06 (if the pulse count is greater than triple of
P93.05, the delay P93.06 is directly skipped), if the
option " Zero servo input slows down" is selected,
the VFD runs downward slowly at the frequency
P93.03 and coasts to stop within the time P93.04.
Then the VFD performs inspection again.
(2) When P93.02=2: Zero servo input is always
valid (keeping running at zero speed).
P93.03 setting range: P90.17 (Reverse brake
release frequency)
–8.00Hz
P93.04 setting range: 0.0s
–30.0s
P93.05 setting range: 0
–20000
P93.04
Slow lowering
hold time
2.0s
○
P93.05
Zero servo
tolerance pulse
threshold
20000
○
P93.06
Brake failure
alarm protection
input delay
0
–20.000s
1.000s
○
P93.07
Brake failure
alarm protection
reset method
0
–1
0: Only for downward running
1: Both for upward and downward running
1
◎
P93.08
Enabling height
measuring
0
–1
0: Disable
1: Enable internal measuring (motor encoder)
2: Enable external measuring (HDI)
0
◎