Function
code
Name
Description
Default
value
asynchronous motor 1 1: Enabled
Note:
The I/F mode is not applicable to conical
motors.
P04.41
Current setting in I/F
mode for
asynchronous motor 1
When I/F control is adopted for asynchronous
motor 1, this parameter is used to set the output
current. The value is a percentage in relative to the
rated current of the motor.
Setting range: 0.0
–200.0%
120.0%
P04.42
Proportional
coefficient in I/F mode
for asynchronous
motor 1
When I/F control is adopted for asynchronous
motor 1, this parameter is used to set the
proportional coefficient of the output current
closed-loop control.
Setting range: 0
–5000
350
P04.43
Integral coefficient in
I/F mode for
asynchronous motor 1
When I/F control is adopted for asynchronous
motor 1, this parameter is used to set the integral
coefficient of the output current closed-loop control.
Setting range: 0
–5000
150
P04.44
Starting frequency for
switching off I/F mode
for asynchronous
motor 1
When I/F control is adopted for asynchronous
motor 1, this parameter is used to set the starting
frequency for switching off the output current
closed-loop control. When the frequency is lower
than the value of this parameter, the current
closed-loop control in the I/F control mode is
enabled; and when the frequency is higher than
that, the current closed-loop control in the I/F
control mode is disabled.
Setting range: 0.00
–20.00 Hz
10.00Hz
P04.45
Enabling I/F mode for
asynchronous motor 2
0: Disable
1: Enable
Note:
The I/F mode is not applicable to conical
motors.
0