Goodrive350-19 series VFD Function parameter list
- 297 -
Function
code
Name
Description
Default
value
Modify
baud rate setup transmission speed between upper computer and
the VFD.
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
6: 57600BPS
7: 115200BPS
Note:
Baud rate of the upper computer must be
the Same as the VFD; otherwise, communication
cannot be performed. The larger the baud rate, the
faster the communication speed.
P14.02
Data bit check
setup
The data format of upper computer must be the
Same as the VFD; otherwise, communication
cannot be performed.
0: No parity check (N, 8, 1) for RTU
1: Even parity (E, 8, 1) for RTU
2: Odd parity (O, 8, 1) for RTU
3: No parity check (N, 8, 2) for RTU
4: Even parity (E, 8, 2) for RTU
5: Odd parity (O, 8, 2) for RTU
1
○
P14.03
Communication
response delay
0
–200ms
It refers to the time interval from when the data is
received by the VFD to the moment when the data
is sent to the upper computer. If the response
delay is less than the system processing time, the
response delay will be subject to system
processing time; if the response delay is longer
than the system processing time, data will be sent
5
○