Goodrive350-19 series VFD Operating
- 135 -
Function
code
Name
Description
Default
value
8: Ethernet communication (the same as above)
9: Pulse frequency HDIB (the same as above)
10: EtherCat/Profinet communication
11: PLC
12: Reserved
Note:
For the options 1-11, 100% is relative to
the max. frequency.
P03.16
Keypad limit value
of upper limit
frequency of
forward rotation in
torque control
0.00Hz
–P00.03 (Max. output frequency)
50.00 Hz
P03.17
Keypad limit value
of upper limit
frequency of
reverse rotation in
torque control
0.00Hz
–P00.03 (Max. output frequency)
50.00 Hz
P03.18
Source of upper
limit setup of the
torque during
motoring
0: Keypad (P03.20)
1: AI1 (100% relative to three times of motor
current)
2: AI2 (the same as above)
3: AI3 (the same as above)
4: Pulse frequency HDIA (the same as above)
5: MODBUS communication (the same as
above)
6: PROFIBUS/CANopen/DeviceNet
communication (the same as above)
7: Ethernet communication (the same as above)
8: Pulse frequency HDIB (the same as above)
9: EtherCat/Profinet communication
10: PLC
0