Goodrive350-19 series VFD Function parameter list
- 251 -
Function
code
Name
Description
Default
value
Modify
60: In motor 1 state
61: In motor 2 state
62: In motor 3 state
63: PT100 temperature alarm
64: PT1000 temperature alarm
65: Boosting the speed with light load
66: Derating the frequency with voltage
P06.05
Output terminal
polarity selection
This function code is used to set the polarity of
output terminals.
When the bit is set to 0, input terminal polarity is
positive;
When the bit is set to 1 input terminal polarity is
negative.
BIT3
BIT2
BIT1
BIT0
RO2
RO1
HDO
Y
Setting range: 0x0
–0xF
00
○
P06.06 Y switch-on delay
This function code defines the corresponding
delay of the level variation from switch-on to
switch-off.
Y electric level
Y valid
Invalid
Switch on
delay
invalid
Valid
Switch off
delay
Setting range: 0.000
–50.000s
Note:
P06.08 and P06.09 are valid only when
P06.00=1.
0.000s
○
P06.07 Y switch-off delay
0.000s
○
P06.08
HDO switch-on
delay
0.000s
○
P06.09
HDO switch-off
delay
0.000s
○
P06.10
Relay RO1
switch-on delay
0.000s
○
P06.11
Relay RO1
switch-off delay
0.000s
○
P06.12
Relay RO2
switch-on delay
0.000s
○