Goodrive350-19 series VFD Function parameter list
- 278 -
Function
code
Name
Description
Default
value
Modify
P09.19
Low frequency
differential time
0.00
–10.00s
0.00s
○
P09.20
Low frequency
point of switching
PID parameters
0
–P09.21
5.00Hz
○
P09.21
High frequency
point of switching
PID parameters
P09.20
–P00.03
10.00Hz
○
7.2.11 P10 Simple PLC and multi-step speed control
Function
code
Name
Description
Default
value
Modify
P10.00 Simple PLC mode
0: Stop after running once; the VFD stops
automatically after running for one cycle, and it
can be started only after receiving running
command.
1: Keep running in the final value after running
once; The VFD keeps the running frequency and
direction of the last section after a single cycle.
2: Cyclic running; the VFD enters the next cycle
after completing one cycle until receiving stop
command and stops.
0
○
P10.01
Simple PLC
memory selection
0: No memory after power down
1: Memory after power down; PLC memories its
running stage and running frequency before power
down.
0
○
P10.02 Multi-step speed 0 Setting range of the frequency in 0
th
–15
th
sections
are -100.0
–100.0%, 100% corresponds to Max.
output frequency P00.03.
Setting range of the running time in 0
th
–15
th
sections are 0.0
–6553.5s (min), the time unit is
0.0%
○
P10.03
Running time of
0
th
step
0.0s(min)
○
P10.04 Multi-step speed 1
0.0%
○